Foundation fieldbus data – KROHNE OPTIFLEX 1300C FOUNDATION FIELDBUS User Manual
Page 4
2
FOUNDATION FIELDBUS DATA
4
OPTIFLEX 1300 C
www.krohne.com
02/2010 - 4000621501 - AD FF OPTIFLEX 1300 R01 en
INFORMATION!
•
The data that follows is applicable only for fieldbus communication networks. For general
data, refer to the handbook.
•
Additional information (certificates, special tools, software, files...) and complete product
documentation is on the CD delivered with the device or can be downloaded free of charge
from the website (Downloadcenter).
Type
TDR level transmitter
Output signal
Digital signal that agrees with the FF communication protocol
Test status
Registered
Data blocks
Registered features
Alarms, events, function blocks, linking and trending
Registered function blocks
1 x Resource Block (RB)
4 x Analog Input Blocks (RB)
Other blocks
1 x Transducer Block (TB)
Communication Standard
Foundation Fieldbus protocol that agrees with IEC 61158-2
ITK version
5.1
Physical layer
Protocol
Foundation Fieldbus protocol that agrees with IEC 61158-2, galvanically isolated
Physical layer types
Standard power signaling, bus powered, non I.S.
Other features
Bus interface with integrated reverse polarity protection
Electrical connections
Device power supply (24 V input)
18...30 VDC
Current consumption on
FOUNDATION Fieldbus network
20 mA
Input and output
Output data
Level, distance, level conversion, level mass, reflection, ullage conversion or
distance mass
Input data
None
Error current FDE
Typically 0 mA (FDE =Fault Disconnection Electronic)
Link Master function
Not supported