ELECTRICAL CONNECTIONS

3

5

OPTIFLEX 1300 C

www.krohne.com

02/2010 - 4000621501 - AD FF OPTIFLEX 1300 R01 en

3.1 Electrical installation: terminals

Electrical connection must agree with IEC 61158-2.

Procedure:

• Remove the housing terminal compartment cover 1.
• Connect the FF segment to the communication terminals 5 and 6 of the device. Obey the

national electrical codes and fieldbus specifications for communication networks.

• Make sure that the polarity of the wires is correct.
• Connect the power supply to the power supply terminals 2 and 3 of the device. Obey the

national electrical codes.

• Make sure that the polarity of the wires is correct.
• Attach the ground to 4 or 7. Both terminals are technically equivalent.

Figure 3-1: Electrical installation

1 Terminal compartment cover
2 Power supply terminal: 24 VDC -
3 Power supply terminal: 24 VDC +
4 Grounding terminal in the housing
5 Communication terminal: -
6 Communication terminal: +
7 Grounding terminal between the process connection and the converter

INFORMATION!
The FF terminal is connected to a Fieldbus Power Hub. The 24 VDC terminal energizes the
device.