1 electrical installation: terminals, Electrical connections – KROHNE OPTIFLEX 1300C FOUNDATION FIELDBUS User Manual
Page 5
ELECTRICAL CONNECTIONS
3
5
OPTIFLEX 1300 C
www.krohne.com
02/2010 - 4000621501 - AD FF OPTIFLEX 1300 R01 en
3.1 Electrical installation: terminals
Electrical connection must agree with IEC 61158-2.
Procedure:
• Remove the housing terminal compartment cover 1.
• Connect the FF segment to the communication terminals 5 and 6 of the device. Obey the
national electrical codes and fieldbus specifications for communication networks.
• Make sure that the polarity of the wires is correct.
• Connect the power supply to the power supply terminals 2 and 3 of the device. Obey the
national electrical codes.
• Make sure that the polarity of the wires is correct.
• Attach the ground to 4 or 7. Both terminals are technically equivalent.
Figure 3-1: Electrical installation
1 Terminal compartment cover
2 Power supply terminal: 24 VDC -
3 Power supply terminal: 24 VDC +
4 Grounding terminal in the housing
5 Communication terminal: -
6 Communication terminal: +
7 Grounding terminal between the process connection and the converter
INFORMATION!
The FF terminal is connected to a Fieldbus Power Hub. The 24 VDC terminal energizes the
device.