beautypg.com

Device description, 4 flammable products, 5 equipment category – KROHNE H250 M40 NEPSI Ex ia User Manual

Page 6: 6 types of protection

background image

2

DEVICE DESCRIPTION

6

H250 M40

www.krohne.com

03/2013 - 4002616701 AD H250 M40 NEPSI Ex ia R01 en

2.4 Flammable products

Atmospheric conditions:

Atmospheric conditions:

Atmospheric conditions:

Atmospheric conditions:

An explosive atmosphere is a mixture of air and flammable gases, vapours, mists or dusts under
atmospheric conditions. The following values define it
T

atm

= -20...+60°C / -4...+140°F and P

atm

= 0.8...1.1 bar.

Outside of this range, no key data are available as to ignition behaviour for most mixtures.

Installation conditions:

Installation conditions:

Installation conditions:

Installation conditions:

Variable area flowmeters operate outside of atmospheric conditions, which means that
explosion protection – regardless of the zone assignment – is fundamentally not applicable due
to the lack of key safety data for the interior of the measuring section.

2.5 Equipment category

The flowmeters are designed according to GB 3836.1-2010 and GB 3836.4-2010.

2.6 Types of protection

The variable-area flowmeter is designed with Intrinsic Safety type of protection, protection level
“ia“.

WARNING!
Operation with flammable products is only permitted as long as no explosive fuel/air mixture
builds up on the inside of the flowmeter under operating conditions. The operator is responsible
for ensuring that the flowmeter is operated safely as regards the temperature and pressure of
the products used. In case of operation with flammable products the measuring units must be
included in the periodic pressure tests of the system. When using the device version H250/C...
(PTFE-liner, nonconductive) the min. conductivity of the medium must be 10

-8

S/m, in order to

avoid the electrostatic charge.

INFORMATION!
Definition of zone 2 acc. to EN 1127-1, Appendix B:
An area in which an explosive atmosphere as a result of the mixture of flammable substances in
the form of gas, steam or mist with air is not expected to occur under normal operation. If,
however, such an atmosphere does occur it only lasts for a brief period of time.

The marking Ex ia IIC T1-T6 Gb

Ex ia IIC T1-T6 Gb

Ex ia IIC T1-T6 Gb

Ex ia IIC T1-T6 Gb contains the following information:

Ex ia

Ex ia

Ex ia

Ex ia

Intrinsic Safety type, protection level “ia“

IIC

IIC

IIC

IIC

suitable for gas group IIC, IIB and IIA

T1-T6

T1-T6

T1-T6

T1-T6

suitable for temperature class T6 ... T1

Gb

Gb

Gb

Gb

EPL, suitable for zone 1

AD_H250_M40_NEPSI_Ex_ia_R01_en_4002616701_PRT.book Page 6 Friday, March 8, 2013 11:14 AM