KROHNE OPTISOUND 3050 Ex ES User Manual

Page 20

background image

English



4.3 Permissible process pressure on the transducer:

The process pressure in hazardous atmospheres must be between 0.8 bar …1.1 bar.
The permissible combinations of pressure and temperature without hazardous mixture are mentioned
in the manufacturer declaration (e.g. the operating manual).


4.4 Protection

class:


Housing protection, housing in zone 21:

IP66

Transducer in zone 20:

IP68



5. Cable entry

Cable entries may only be replaced by same types or separately certified EEx e resp. Ex d cable
entries with min. protection IP66 which are suitable for the certified temperatures of OPTISOUND
3040/3050 C VF3*4.GX***VD**X .

The supplied or installed cable entry is suitable for the housing temperature range mentioned in the
OPTISOUND 3040/3050 C VF3*4.GX***VD**X certification.
If another cable entry is used, the separately certified cable entry determines the max. permissible
ambient temperature on the electronics housing (max. values: -40°C, +60°C).


6. Electrostatics

The transducer housing OPTISOUND 3040/3050 C VF3*4.GX***VD**X consists of electrically
conductive plastic and is integrated in the potential equalization (inclusively metallic diaphragm and
mounting element).


7. Material resistance

For applications requiring category 1/2 D or 2 D instruments OPTISOUND 3040/3050 C
VF3*4.GX***VD**X must only be used in products against which the wetted parts are sufficiently
resistant.


8. Grounding

OPTISOUND 3040/3050 C VF3*4.GX***VD**X must be grounded.


9. Housing cover locking

For the double chamber housing please make sure that prior to the set-up the housing cover of the
connection compartment and the electronics compartment must be screwed in up to the stop and has
to be secured with the cover locking.

20 30667-DE-050920

OSOUND3040-3050C-G_V