Technical data, profibus ident-no. f401, Hardware, Connectionindependent of polarity – KROHNE IFC 090 Converter PROFIBUS PA EN User Manual
Page 7: Software, Address range0-126, default 126, “set slave add, Menu settings for profibus-pa, Ii d d, Technical data, Di i
Supplementary Documentation IFC 090, IFC 090 i with PROFIBUS-PA
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5
D-47058 Duisburg
7/7
Tel.: 0203-301 309 Fax: 0203-301389 · e-mail: [email protected]
PROFIBUS-PA with current output
PROFIBUS-PA with pulse/switching output
Non Ex version
Non Ex version
Ex version
Ex version
current
output
fieldbus
power-
supply
D
D
I
I
U min
= 8V
U max = 30V
4-20mA
FE
FE
bus-
connection
switching
output
fieldbus
power-
supply
B
1
B
1
bus-
connection
D
D
FE
FE
I
I D D
current
output
fieldbus
power
supply
U min
= 8V
bus-
connection
U max = 30V
4-20mA
B
1
D D
switching
output
fieldbus
power
supply
bus-
connection
B
1
3. Menu settings for PROFIBUS-PA
(see Section 4 in the Installation and Operating Instructions)
The following settings need to be made for operation of the IFC 090 on a PROFIBUS-PA network. Note that the
address can be set by the service “set slave address” as well.
Function (Fct.) Description
3.8 TAG NO.
Text, measuring-point tag (max. 10 characters)
Characters assignable to each place:
¨ A-Z,a-z, 0-9 or "_" (blank character)
3.9 COM
Select function for the communication port
¨ OFF
¨ HART
¨ PROFI PA
Press key to transfer to subfunction "ADDRESS".
ADDRESS Set
address
Range:
00-15 for HART (default 00)
00-126 for PROFI PA (default 126)
Press key to return to Fct. 3.9 COM
4. Technical data
, PROFIBUS Ident-No. F401
Hardware
Physical
to IEC 61158-2 and the FISCO model
Bus characteristics
9... 30 V; 0.3 A max.; 4.2 W max.
Base current
10 mA
FDE
yes: separate fault clearance
electronics
provided
Fault current
6 mA; (fault current = max. continuous
current – base current)
Starting current
lower than the base current
“Ex“ approval
EEx ia IIC T6 or EEx ib IIC/IIB T6 in
conformity with the FISCO model
Connection
independent of polarity
Software
GSD
all KROHNE GSD files supplied on
diskette
Device profile
complete implementation of Profile B, V2.0
Functional blocks flow [m3/h], totalizer1[m3], totalizer2 [m3]
mentioned units are default units
Address range
0-126, default 126,
“set slave address” supported
Operator control local display and operator interface at
device
SAP`s
1; typically the number of service access
points is equal to the number of class 2
masters (operating tools)