beautypg.com

Technical data, profibus ident-no. f401, Hardware, Connectionindependent of polarity – KROHNE IFC 090 Converter PROFIBUS PA EN User Manual

Page 7: Software, Address range0-126, default 126, “set slave add, Menu settings for profibus-pa, Ii d d, Technical data, Di i

background image

Supplementary Documentation IFC 090, IFC 090 i with PROFIBUS-PA

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5

  D-47058 Duisburg

7/7

Tel.: 0203-301 309 Fax: 0203-301389 · e-mail: [email protected]


PROFIBUS-PA with current output

PROFIBUS-PA with pulse/switching output

Non Ex version









Non Ex version

Ex version











Ex version

current

output

fieldbus

power-
supply

D

D

I

I

U min
= 8V

U max = 30V

4-20mA

FE

FE

bus-
connection

switching

output

fieldbus

power-
supply

B

1

B

1

bus-
connection

D

D

FE

FE

I

I D D

current

output

fieldbus

power
supply

U min
= 8V

bus-
connection

U max = 30V

4-20mA

B

1

D D

switching

output

fieldbus

power
supply

bus-
connection

B

1

3. Menu settings for PROFIBUS-PA

(see Section 4 in the Installation and Operating Instructions)

The following settings need to be made for operation of the IFC 090 on a PROFIBUS-PA network. Note that the
address can be set by the service “set slave address” as well.

Function (Fct.) Description

3.8 TAG NO.

Text, measuring-point tag (max. 10 characters)
Characters assignable to each place:
¨ A-Z,a-z, 0-9 or "_" (blank character)

3.9 COM

Select function for the communication port

¨ OFF

¨ HART

¨ PROFI PA

Press key to transfer to subfunction "ADDRESS".

ADDRESS Set

address

Range:

00-15 for HART (default 00)
00-126 for PROFI PA (default 126)

Press key  to return to Fct. 3.9 COM

4. Technical data

, PROFIBUS Ident-No. F401

Hardware
Physical

to IEC 61158-2 and the FISCO model

Bus characteristics

9... 30 V; 0.3 A max.; 4.2 W max.

Base current

10 mA

FDE

yes: separate fault clearance

electronics

provided

Fault current

6 mA; (fault current = max. continuous

current – base current)

Starting current

lower than the base current

“Ex“ approval

EEx ia IIC T6 or EEx ib IIC/IIB T6 in

conformity with the FISCO model

Connection

independent of polarity

Software
GSD

all KROHNE GSD files supplied on
diskette

Device profile

complete implementation of Profile B, V2.0

Functional blocks flow [m3/h], totalizer1[m3], totalizer2 [m3]

mentioned units are default units

Address range

0-126, default 126,
“set slave address” supported

Operator control local display and operator interface at

device

SAP`s

1; typically the number of service access
points is equal to the number of class 2
masters (operating tools)