beautypg.com

KROHNE ALTOFLUX IFM 6080 K EEx EN User Manual

Page 10

background image

10

9 Technical

data

See also the standard Installation and operating instructions.

Rated pressure

See typeplate

Ambient temperature:

-20..50/60

°

C, see Certificate of Conformity or following table.

Medium temperature:

See Certificate of Conformity or following table.

Max. ambient temperature

[

°

C]

Temperature class

Max. Medium temperature

[

°

C]

50

T6
T5
T4
T3

70

85
120
180

60

T6
T5
T4
T3

70
85

100
100

Note:
The maximum medium temperatures listed in the table above are safety-technical limits! Due to
function-technical reasons lower limits may prevail.

10 Maintenance

The IFM 6080 K / i- EEx compact flowmeters are maintenance free with regard to flowmetering
properties.

Within the scope of the periodic inspections required for electrical apparatus in hazardous areas, it
is recommended to check the flameproof enclosures for external damage and signs of corrosion.
Opening of the housing of the primary head (coil housing) is not allowed, as this will nullify the
used type of protection for the explosion safety. There are also no serviceable parts inside the
primary head.