Supplement to Installation and Operating Instructions H 250/ESK3-PA

KROHF201.GSD

KROHNE supplies you the with the GSD with complete device functionality which is shown
in the following table:

Block Number

Assignment

KROHF201.GSD
Ident No. F201

Address for the
“channel parameter”

1

Volume flowrate

1)

Mass flowrate

AI(0)-FB

0x0111
0x0115

2

Volume meter

TOT(0)-FB

0x0111 (fixed)

3

Mass meter

TOT(1)-FB

0x0115 (fixed)

AI = Analog input
TOT = Totalizer
FB = Function block

1)

Standard assignment;

AI-FB can transmit volume or mass flowrate by changing the corresponding address for
the “channel parameter” .
To be able to change the standard assignment (volume flowrate) you must have an
operating tool which can modify the “channel parameter” of the function block. You
can find the “channel parameter” in the AI function block under the relative index 14.
In the above table, in the column headed “Address for the channel parameter”,
you can find the value which you must enter into the function block.
As part of the manufacturer’s specific configuration (Identnumber 0xF201) there are usually
two meters available; TOT(0) as volume meter and TOT(1) as mass meter.
The generic configuration (Identnumber 0x9740) is only available for the volume meter.