Supplement to Installation and Operating Instructions H 250/ESK3-PA

4

Technical data

Hardware
Physics

to IEC 61158-2, and the FISCO model

Supply voltage
2 wire bus connection,
not polarity sensitive

9 ... 32 V DC *

Power consumption
Basic current

12 mA

Start-up current

< basic current

FDE (fault disconnect electronics),
power in case of single error

< 18 mA

Accuracy
In connection with H250/M9

Class 1.6

Measurement resolution

< 0.1 % of full scale range

Temperature effect

< 0.05 %/K of full scale range

EU type approval certificate
II 2 G EEx ia IIC T6

PTB 00 ATEX 2063

* Supply voltage when used
in potentially explosive areas

max. 24 V DC

Software
GSD
Device master file

is supplied on floppy
or from the Internet

http://www.krohne.com

Device profile

complete realization Profile B, V3.0

Function blocks
Flowrate (AI0)

options of volume or mass flowrate
selected using Channel Parameter
Default units: Qv [m3/h]; Qm [kg/h]

Totalizer (TOT0)

Volume counter
Default unit: [m

3

]

Totalizer (TOT1)

Mass counter
Default unit: [kg]

Address range

0 ... 126 (default = 126)
“Set slave address” is supported

SAP´s
Service access points

1

DD
Device Description

DD for PDM (in preparation)

Operation

using PROFIBUS-PA
(no operator control at device)