4 recurring test and function test – KROHNE OPTISWITCH 5200C 2wire EN User Manual

Page 22

background image

Mode on

the signal

condition-

ing instru-

ment

Level

Signal

current -

Sensor

Analogue

input con-

trol

1)

Signal

lamp -

sensor

Signal

lamp -

signal

condi-

tioning

instru-

ment

Mode A

Overfill

protection

approx.

8 mA

>3.6 mA

<11 mA

Green

Mode A

Overfill

protection

approx.

16 mA

>13 mA

<21 mA

red

Mode B

Dry run

protection

approx.

16 mA

>13 mA

<21 mA

red

Mode B

Dry run

protection

approx.

8 mA

>3.6 mA

<11 mA

Green

Fault signal

(mode A/B)

any

approx.

1.8 mA

<=3.6 mA

>=21.6 mA

6.4 Recurring test and function test

Acc. to WHG and IEC 61508. The implementation of the

recurring test acc. to WHG is stipulated in the general type

approval, item 8.
Take note of the overwhelming approvals, if OPTISWITCH

5200 C, 5250 C Ex is used as part of an overfill protection

system according to WHG.
OPTISWITCH 5200 C, 5250 C Ex in conjunction with an SU

501 (Ex) is qualified in mode A (overfill protection) for use in

measuring chains of SIL2 acc. to IEC 61508 (redundant, SIL3).

1)

Electronics directly evaluated via the analogue input of a control system

(without signal conditioning instrument)

22

OPTISWITCH 5200 C, 5250 C - with two-wire output

Set up

30435

-EN
-060831