beautypg.com

6 set up, 1 general, 2 adjustment elements – KROHNE OPTISWITCH 5100C Relay EN User Manual

Page 18

background image

6 Set up

6.1 General

The numbers in brackets refer to the following illustrations.

The switching condition of the electronics can be checked on

the plastic housing with closed housing cover (control lamp). In

the basic setting, products with a density >0.7 g/cm³

(>0.025 lbs/in³) can be detected. For products with lower

density, the switch must be set to >0.5 g/cm³ (>0.018 lbs/in³).
On the electronics module you will find the following indicating

and adjustment elements:

l

Signal lamp (1)

l

DIL switch for mode adjustment - A/B (2)

l

DIL switch for sensitivity adjustment (3)

Note:

For test purposes, immerse the tuning fork of OPTISWITCH

5100 C, 5150 C always in liquids. Do not test the function of

OPTISWITCH 5100 C, 5150 C with the hand. This can

damage the sensor.

6.2 Adjustment elements

1

2

3

4

5

6

7

8

1

2

3

Fig. 11: Oscillator SWE60R - Relay output

1

Signal lamp (LED)

2

DIL switch for mode adjustment

3

DIL switch for sensitivity adjustment

Function/Configuration

18

OPTISWITCH 5100 C, 5150 C - with relay output

Set up

30426

-EN
-060831