beautypg.com

3 operation – KROHNE OPTISWITCH 3200C 2wire EN User Manual

Page 8

background image

It is designed for industrial use in all areas of process

technology and is preferably used for bulk solids.
Typical applications are overfill and dry run protection. Thanks

to its simple and robust measuring system, OPTISWITCH

3200 C is virtually unaffected by the chemical and physical

properties of the bulk solid.
It functions even when exposed to strong external vibration or

changing products.
Solid detection in water

If OPTISWITCH 3200 C was ordered for detection of solids in

water, the tuning fork is adjusted to the density of water. In the

air or when covered by water (density: 1 g/cm³/0.036 lbs/in)

OPTISWITCH 3200 C signals "uncovered". Only if the

vibrating element is also covered with solids (e.g. sand,

sludge, gravel etc.) will the sensor signal "covered".
Fault monitoring

The electronics of OPTISWITCH 3200 C continuously mon-

itors the following criteria:

l

Correct vibrating frequency

l

Line break to the piezo drive

If one of these faults is detected, the electronics signals this via

a defined current to the signal conditioning instrument. The

connection cable to the vibrating element is also monitored.

The tuning fork is piezoelectrically energised and vibrates at its

mechanical resonance frequency of approx. 150 Hz. When the

tuning fork is submerged in the product, the vibration

amplitude changes. This change is detected by the integrated

oscillator and converted into a switching command.

Depending on your requirements, OPTISWITCH 3200 C with

two-wire electronics can be connected to different signal

conditioning instruments. Compatible signal conditioning in-

struments are listed under "Technical data".
The exact range of the power supply is stated in the "Technical

data" in the "Supplement".

3.3 Operation

With the factory setting, products with a density of >0.02 g/cm³

(>0.0008 lbs/in³) can be measured. The instrument can also

be adapted to products with lower density >0.008 g/cm³

(>0.0003 lbs/in³).

Physical principle

Power supply

8

OPTISWITCH 3200 C - with two-wire output

Product description

29959

-EN
-060830