beautypg.com

3 exchange the electronics – KROHNE OPTISWITCH 3200C 2wire EN User Manual

Page 26

background image

l

Wrong mode selected

à

Set the mode switch on OPTISWITCH 3200 C to

"max". Set the correct mode on the signal conditioning

instrument (A: overfill protection; B: dry run protection).

?

Signal lamp flashes red

l

Electronics has detected a failure

à

Exchange instrument or return instrument for repair

7.3 Exchange the electronics

In general, all oscillators of series WE60 can be interchanged.

If you want to use an oscillator with a different signal output,

you can download the corresponding operating instructions

manual from our homepage under Downloads.

With EEx d instruments, the housing cover must only be

opened if there is no explosive atmosphere.

Proceed as follows:
1 Switch off power supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10

or slot 4)

2

1

Fig. 13: Loosen the screws

1

Electronics module

2

Screws (2 pcs.)

26

OPTISWITCH 3200 C - with two-wire output

Maintenance and fault rectification

29959

-EN
-060830