- Standard

>0.02 g/cm³ (0.0007 lbs/in³)

- adjustable

>0.008 g/cm³ (0.0003 lbs/in³)

Electromechanical data
Cable entry/plug

1)

- Single chamber housing

l

1x cable entry M20x1.5 (cable-ø 5 … 9 mm),

1x blind stopper M20x1.5

or:

l

1x closing cap ½ NPT, 1x blind plug ½ NPT

or:

l

1x plug (depending on the version), 1x blind

plug M20x1.5

Spring-loaded terminals

for wire cross-section up to 1.5 mm²

(0.0023 in²)

Adjustment elements
Mode switch
- min.

Min. detection or dry run protection

- max.

Max. detection or overfill protection

Voltage supply
Supply voltage

10 … 55 V DC

Power consumption

max. 0.5 W

Electrical protective measures
Protection

IP 66/IP 67

Overvoltage category

III

Protection class

II

Approvals

2)

ATEX II 1/2G, 2G EExd d IIC T6
ATEX II 1/2 D IP66 T

1)

Depending on the version M12x1, according to DIN 43650, Harting, Am-

phenol-Tuchel, 7/8" FF.

2)

Deviating data in Ex applications: see separate safety instructions.

Supplement

28

OPTISWITCH 3100 C - with transistor output

29954

-EN
-060830