beautypg.com

3 exchange the electronics – KROHNE OPTISWITCH 3100C Transistor EN User Manual

Page 23

background image

l

Wrong mode selected

à

Set the correct mode on the mode switch (max.: overfill

protection; min.: dry run protection). Wiring should be

carried out according to the quiescent current principle.

?

Signal lamp flashes red

l

Electronics has detected a failure

à

Exchange instrument or return instrument for repair

7.3 Exchange the electronics

In general, all oscillators of series WE60 can be interchanged.

If you want to use an oscillator with a different signal output,

you can download the corresponding operating instructions

manual from our homepage under Downloads.

With EEx d instruments, the housing cover must only be

opened if there is no explosive atmosphere.

Proceed as follows:
1 Switch off power supply
2 Unscrew the housing cover
3 Lift the opening levers of the terminals with a screwdriver
4 Pull the connection cables out of the terminals
5 Loosen the two screws with a screw driver (Torx size T10

or slot 4)

2

1

Fig. 15: Loosen the screws

1

Electronics module

2

Screws (2 pcs.)

OPTISWITCH 3100 C - with transistor output

23

Maintenance and fault rectification

29954

-EN

-060830