7 Maintenance and fault rectification

7.1 Maintenance

When used as directed in normal operation, OPTISWITCH

3100 C is completely maintenance free.

7.2 Rectify faults

OPTISWITCH 3100 C offers maximum reliability. Nevertheless

faults can occur during operation. These may be caused by the

following, e.g.:

l

Sensor

l

Process

l

Power supply

l

Signal processing

The first measure to be taken is to check the output signal. In

many cases, the causes can be determined this way and the

faults rectified.

?

OPTISWITCH 3100 C signals "covered" when the vibrating

element is not submerged (overfill protection)

?

OPTISWITCH 3100 C signals "uncovered" when the

vibrating element is submerged (dry run protection)

l

Supply voltage too low

à

Check the power supply

l

Electronics defective

à

Press the mode switch (min./max.). If the instrument

then changes the mode, the instrument may be

mechanically damaged. Should the switching function

in the correct mode still be faulty, return the instrument

for repair.

à

Push the mode switch. If the instrument then does not

change the mode, the oscillator may be defective.

Exchange the oscillator.

à

Check if there is buildup on the vibrating element, and if

so, remove it.

l

Unfavourable installation location

à

Mount the instrument at a location in the vessel where

no dead zones or mounds can form.

à

Check if the vibrating element is covered by buildup on

the socket.

Causes of malfunction

Fault rectification

Checking the switching signal