5 Connecting to voltage supply

5.1 Preparing the connection

Generally not the following safety instructions:

l

Connect only in the complete absence of line voltage

Connect the power supply according to the following diagrams.

Oscillator VB60R is designed in protection class 1. To maintain

this protection class, it is absolutely necessary that the ground

conductor is connected to the internal ground terminal. Take

note of the general installation regulations. As a rule, connect

OPTISWITCH 3000 C to vessel ground (PA), or in case of

plastic vessels, to the next ground potential. On the side of the

housing there is a ground terminal between the cable entries.

This connection serves to drain off electrostatic charges.
The data for power supply are stated in the "Technical data"

in the "Supplement".

OPTISWITCH 3000 C is connected with standard cable with

round cross section. An outer cable diameter of 5 ... 9 mm

(0.2 ... 0.35 in) ensures the seal effect of the cable gland.
If cable with a different diameter or wire cross section is used,

exchange the seal or use an appropriate cable connection.

5.2 Connection steps

Proceed as follows:
1 Unscrew the housing cover
2 Loosen compression nut of the cable entry
3 Remove approx. 10 cm (4 in) of the cable mantle, strip

approx. 1 cm (0.4 in) insulation from the ends of the

individual wires

4 Insert the cable into the sensor through the cable entry
5 Lift the opening levers of the terminals with a screwdriver

(see following illustration)

6 Insert the wire ends into the open terminals according to

the wiring plan

7 Press the opening lever of the terminals downward, you will

hear the terminal spring closing

8 Check the hold of the wires in the terminals by lightly

pulling on them

Note safety instructions

Select power supply

Selecting the connection ca-

ble

OPTISWITCH 3000 C - with relay output

13

Connecting to voltage supply

30059

-EN

-060830