3

ELECTRICAL CONNECTIONS

24

OPTIFLEX 2200 C/F

www.krohne.com

04/2013 - 4000861602 - AD ATEX OPTIFLEX 2200 R02 en

3.6 Ex d ia / Ex ia tb equipment

3.6.1 General notes

Ex d ia- and Ex ia tb-approved equipment have two separate compartments. The electronics in
the electronics block compartment are Ex ia-approved and the terminals compartment is Ex d /
Ex t-approved.

Figure 3-7: Compact version: Compartments in Ex d ia- and Ex ia tb-approved equipment

Figure 3-8: Remote (Field) version: Compartments in Ex d ia- and Ex ia tb-approved equipment

1 Electronics block (Ex ia) compartment
2 Terminal (Ex d / Ex t) compartment

INFORMATION!
The flamepath dimensions are better than the values specified in the European Standard
EN 60079-1 (minimum length 13.9 mm and maximum gap 118

µ

m).