Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [–>] key.

A linearization is necessary for all vessels in which the vessel

volume does not increase linearly with the level – e.g. in a

cylindrical or spherical tank -–and the indication or output of

the volume is requested. Corresponding linearization curves

are preprogrammed for these vessels. They represent the

correlation between the level percentage and vessel volume.

By activating the appropriate curve, the volume percentage of

the vessel is displayed correctly. If the volume should not be

displayed in percent but e.g. in l or kg, a scaling can be also

set in the menu item "Display".

Linearization curve

Linear

Enter the requested parameter via the appropriate keys, save

your settings and jump to the next menu item with the [–>] key.

In this menu item you can enter an unambiguous designation

for the sensor, e.g. the measurement loop name or the tank or

product designation. In digital systems and in the documen-

tation of larger plants, a singular designation should be entered

for exact identification of individual measuring sites.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is finished and you

can now jump to the main menu with the [ESC] key.

High sockets or vessel installations, such as e.g. struts or

agitators as well as buildup and weld joints on the vessel walls

cause interfering reflections which can impair the measure-

ment. A false signal suppression detects, marks and saves

these false signals, so that they are no longer taken into

account for the level measurement. This false signal sup-

pression should be created with empty vessel so that all

potential interfering reflections will be detected.

Linearization curve

Sensor-TAG

False signal suppression

30

OPTISOUND 3030 C - 4 … 20 mA/HART

Setup with the indicating/adjustment module