More than 1 FMCW radar level meter can be operated in a silo.

2.8 Installation recommendations for solids

Figure 2-9: Product inlets

1 The device is in the correct position.
2 The device is too near to the product inlet.

Figure 2-10: More than 1 FMCW radar level meter can be operated in a silo

CAUTION!
Do not install the device above objects in the silo (ladder, supports etc.). Objects in the silo can
cause parasite radar signals. If there are parasite radar signals, the device will not measure
correctly.
If it is not possible to install the device on another part of the silo, do an empty spectrum scan.

INFORMATION!
We recommend that you configure the device when the silo is empty.

INFORMATION!
For the best device performance, the antenna should be silo-intrusive. Refer to the illustration
that follows.