2

DEVICE DESCRIPTION

10

OPTISWIRL 4070

www.krohne.com

04/2013 - 4000077105 MA OPTISWIRL4070 II2G AD R05 en

2.8 Electrical data

Signal circuits

Signal circuits

Signal circuits

Signal circuits

The vortex flowmeter signal circuits may only be connected to separate, intrinsically safe
circuits. The maximum permissible values considered safe are listed below. The connection may
only be made using separately certified intrinsically safe isolating amplifiers or zener barriers
with the following maximum values per circuit:

• U

i

= 30 V

• I

i

= 100 mA

• P

i

= 1,0 W

The following values are to be observed for each intrinsically safe circuit in case of
interconnection:

• C

i

= 15 nF

• L

i

≈ 600 µH

Sensor circuits

Sensor circuits

Sensor circuits

Sensor circuits

With the compact device, the intrinsically safe sensor circuits are designed as internal circuits.

When it comes to the remote versions, the intrinsically safe sensor circuits are led through. The
maximum permissible values of the sensor circuits considered safe are listed below:

Piezo / Pt1000 circuit

• U

o

= 30 V

• I

o

= 62 mA

• P

o

= 340 mW

• C

o

= 22 nF

• L

o

= 0,35 mH

Pressure transmitter circuit

• U

o

= 30 V

• I

o

= 100 mA

• P

o

= 509 mW

• C

o

= 44 nF

• L

o

= 0,4 mH