Safety-related characteristics – KROHNE DK 32-DK 34-DK 37 Safety V2 EN User Manual
Page 17
SAFETY-RELATED CHARACTERISTICS
7
17
DK32 - DK34 - DK37
www.krohne.com
06/2013 - 4000574703 MA DK32 34 37 SIL R03 en
DK37/M8E
DK37/M8E
DK37/M8E
DK37/M8E...-SE with 4...20mA current output
DK37/M8E
DK37/M8E
DK37/M8E
DK37/M8E/R*...-SE with 4...20mA current output and dp-regulator
Fail safe
Fail dangerous
detected
undetected detected
undetected
λ
SD
λ
SU
λ
DD
λ
DU
SFF 2
DC
D
SIL AC
3
Stress profile 2
0 FIT
0 FIT
150 FIT
200 FIT
42%
42%
-
Stress profile 4
0 FIT
0 FIT
150 FIT
220 FIT
40%
40%
-
T[Proof] 4
1 year
5 years
10 years
PFD
AVG
5
9.58*10
-4
4.43*10
-3
8.76*10
-3
Fail safe
Fail dangerous
detected
undetected detected
undetected
λ
SD
λ
SU
λ
DD
λ
DU
SFF 2
DC
D
SIL AC
3
Stress profile 2
0 FIT
0 FIT
150 FIT
288 FIT
34%
34%
-
Stress profile 4
0 FIT
0 FIT
150 FIT
338 FIT
30%
30%
-
T[Proof] 4
1 year
5 years
10 years
PFD
AVG
5
1.38*10
-3
6.37*10
-3
1.26*10
-2
2
The number listed is for reference only. The SFF must be determined for the complete
subsystem.
3
SIL AC (architectural constraints) means that the calculated values are within the range
for hardware architectural contraints for the corresponding SIL level.
4
It is assumed that proof testing is performed with a proof test coverage of 99%.
5
The PFD
AVG
was calculated for profile 2 using the Markov modelling. The results must
be considered in combination with PFD
AVG
values of other devices of the Safety
Instrumented Function (SIF) in order to determine suitability for a specific Safety
Integrity Level (SIL)
For SIL1 applications, the PFD
AVG
value needs to be < 10
-1
.
For SIL2 applications, the PFD
AVG
value needs to be < 10
-2
.
MA_DK32_34_37_SIL_R03_en_574703_PRT.book Page 17 Wednesday, June 26, 2013 9:17 AM