SAFETY-RELATED CHARACTERISTICS

7

15

DK32 - DK34 - DK37

www.krohne.com

06/2013 - 4000574703 MA DK32 34 37 SIL R03 en

DK37/M8M

DK37/M8M

DK37/M8M

DK37/M8M/K*...-SK with 1 or 2 fail-safe limit switches 1

Fail safe

Fail dangerous

detected

undetected detected

undetected

λ

SD

λ

SU

λ

DD

λ

DU

SFF 2

SIL AC 3

Stress profile 2

0 FIT

56 FIT

0 FIT

97 FIT

36%

SIL1

Stress profile 4

0 FIT

57 FIT

0 FIT

136 FIT

29%

SIL1

T[Proof] 4

1 year

5 years

10 years

PFD

AVG

5

4.63*10

-4

2.15*10

-3

4.25*10

-3

1

The switching contact output is connected to a fail-safe NAMUR amplifier (e.g. Pepperl
& Fuchs KF**-SH-Ex1). The failure rates of the amplifier are not included in the listed
failure rates.

2

The number listed is for reference only. The SFF must be determined for the complete
subsystem.

3

SIL AC (architectural constraints) means that the calculated values are within the range
for hardware architectural contraints for the corresponding SIL level.

4

It is assumed that proof testing is performed with a proof test coverage of 99%.

5

The PFD

AVG

was calculated for profile 2 using the Markov modelling. The results must

be considered in combination with PFD

AVG

values of other devices of the Safety

Instrumented Function (SIF) in order to determine suitability for a specific Safety
Integrity Level (SIL)
For SIL1 applications, the PFD

AVG

value needs to be < 10

-1

.

For SIL2 applications, the PFD

AVG

value needs to be < 10

-2

.

MA_DK32_34_37_SIL_R03_en_574703_PRT.book Page 15 Wednesday, June 26, 2013 9:17 AM