Safety-related characteristics – KROHNE DK 32-DK 34-DK 37 Safety V1 EN User Manual
Page 16
7
SAFETY-RELATED CHARACTERISTICS
16
DK32 - DK34 - DK37
www.krohne.com
02/2012 - 4000574702 MA DK32 34 37 SIL R02 en
DK37/M8E
DK37/M8E
DK37/M8E
DK37/M8E...-SE with 4...20mA current output
DK37/M8E
DK37/M8E
DK37/M8E
DK37/M8E/R*...-SE with 4...20mA current output and dp-regulator
Fail safe
Fail dangerous
detected
undetected detected
undetected
λ
SD
λ
SU
λ
DD
λ
DU
SFF 2
DC
D
SIL AC
3
Stress profile 2
0 FIT
258 FIT
150 FIT
200 FIT
67.1%
43%
SIL1
Stress profile 4
0 FIT
317 FIT
150 FIT
220 FIT
67.9%
41%
SIL1
T[Proof] 4
1 year
5 years
10 years
PFD
AVG
5
9.58*10
-4
4.43*10
-3
8.76*10
-3
Fail safe
Fail dangerous
detected
undetected detected
undetected
λ
SD
λ
SU
λ
DD
λ
DU
SFF 2
DC
D
SIL AC
3
Stress profile 2
0 FIT
395 FIT
150 FIT
288 FIT
65.3%
34%
SIL1
Stress profile 4
0 FIT
543 FIT
150 FIT
338 FIT
67.2%
31%
SIL1
T[Proof] 4
1 year
5 years
10 years
PFD
AVG
5
1.38*10
-3
6.37*10
-3
1.26*10
-2
2
The number listed is for reference only. The SFF must be determined for the complete
subsystem.
3
SIL AC (architectural constraints) means that the calculated values are within the range
for hardware architectural contraints for the corresponding SIL level.
4
It is assumed that proof testing is performed with a proof test coverage of 99%.
5
The PFD
AVG
was calculated for profile 2 using the Markov modelling. The results must
be considered in combination with PFD
AVG
values of other devices of the Safety
Instrumented Function (SIF) in order to determine suitability for a specific Safety
Integrity Level (SIL)
For SIL1 applications, the PFD
AVG
value needs to be < 10
-1
.
For SIL2 applications, the PFD
AVG
value needs to be < 10
-2
.
MA_DK32_34_37_SIL_R02_en_574702_PRT.book Page 16 Thursday, March 1, 2012 9:53 AM