SAFETY-RELATED CHARACTERISTICS
7
13
DK32 - DK34 - DK37
www.krohne.com
02/2012 - 4000574702 MA DK32 34 37 SIL R02 en
DK32
DK32
DK32
DK32/R*/K*...-SK with 1 or 2 fail-safe limit switches 1 and with dp-regulator
Fail safe
Fail dangerous
detected
undetected detected
undetected
λ
SD
λ
SU
λ
DD
λ
DU
SFF 2
SIL AC 3
Stress profile 2
0 FIT
371 FIT
0 FIT
185 FIT
66.7%
SIL2
Stress profile 4
0 FIT
519 FIT
0 FIT
252 FIT
67.3%
SIL2
T[Proof] 4
1 year
5 years
10 years
PFD
AVG
5
8.83*10
-4
4.09*10
-3
8.10*10
-3
1
The switching contact output is connected to a fail-safe NAMUR amplifier (e.g. Pepperl
& Fuchs KF**-SH-Ex1). The failure rates of the amplifier are not included in the listed
failure rates.
2
The number listed is for reference only. The SFF must be determined for the complete
subsystem.
3
SIL AC (architectural constraints) means that the calculated values are within the range
for hardware architectural contraints for the corresponding SIL level.
4
It is assumed that proof testing is performed with a proof test coverage of 99%.
5
The PFD
AVG
was calculated for profile 2 using the Markov modelling. The results must
be considered in combination with PFD
AVG
values of other devices of the Safety
Instrumented Function (SIF) in order to determine suitability for a specific Safety
Integrity Level (SIL)
For SIL1 applications, the PFD
AVG
value needs to be < 10
-1
.
For SIL2 applications, the PFD
AVG
value needs to be < 10
-2
.