Caution: Observe correct polarity when terminating all input/output wiring. Failure to do so may result in
circuit damage on power up. Seethe field wiring diagram below for terminal locations.

4. Connect 117VAC to the connector labeled “117VAC IN”.
5. If applicable, connect 24 VDC battery backup to the connector labeled “24 VDC IN”.
6. If applicable, connect a remote recording device or computer to the 4-20 mA signal output connector.
The terminals are labeled SENSOR “–” and “mA”.
7. If applicable, connect alarm devices. Discreet alarm relay contacts are provided for three alarms: Fault,
Low and High. The contacts consist of common and choice of normally open or normally closed. Contact
output selections are jumper programmable on the sensor connector board. See the sensor manual for con-
tact ratings and other information.
8. If applicable, connect flow fault alarm wiring. Two sets of form C contacts (common, normally open and
normally closed) are provided. Relay contacts are rated 1 amp at 30VDC/.24 amp at 125VDC.

1.2 START UP

Upon completion of all tubing connections and field wiring turn on the power switch located on the enclo-
sure door. Note that the power lamp illuminates. If applicable, note that the sensor LCD indicators activate.
Varying readings may occur during sensor warm-up. Allow approximately 1 hour to stabilize (24 hours is best).

Detcon Model 971-04117-0LA Gas Detection System PG.4

P7

P8

P6

P5

L1 L2 GND

mA

C NO/NC C NO/NC C NO/NC

117 VAC

IN

24 VDC

IN

Battery

Backup

SENSOR #1

FAULT

ALARM CONTACTS #1

ALARM 1 ALARM 2

ALARM DRY

CONTACTS

COM

NO/NC

COM

COM

NO/NC

NO/NC

FLT ALM 1 ALM 2

Flow

Fault

Circuit

COM

NO

NC

1

COM

NO

NC

2

COM

NO

NC

3

PT1

mA

4-20mA

Wire alarms and the 4-20mA output
signal to the plug-type connectors.

Wire 117 VAC & optional 24 VDC
backup to the lugless connectors.

Two discreet form C dry contacts
are provided (2 & 3) by the flow
fault circuit for alarm devices. The
first set of contacts (1) are
prewired to interrupt the 4-20mA
signal output in the event of a
flow fault. This will allow for flow
fault monitoring at any
controller/computer that the signal
is wired in to.