Detcon FL-10 User Manual
Page 4
Warranty
Two years
Five year f ixed fee service policy
Outputs
Analog 4-20 mA DC
Serial RS-485 Modbus™
Relays
Contacts include common, normally open, and normally closed for three alarms
Resistive load: 5A, 250 VAC; 5A, 30 VDC
Inductive load: 2A, 250 VAC; 2A, 30 VDC
Max. operating current: 5A
2.2 C
ONTROLLER
M
ODELS
The label on the Model FL10 face plate is red. It can be used with any industry standard 4-20 mA f lame detector.
2.3 A
LARM
F
UNCTIONS AND
C
ONTROLLER
C
ONFIGURATION
Model FL10 control modules incorporate several user selectable alarm programming options and general operating
options that are accomplished via dip switches. These options include latching of relays, energized/de-energized relays,
and alarm f iring direction. Reference the f igure below for the applicable dip switch locations and settings.
2
2..3
3..1
1 L
La
attc
ch
hiin
ng
g o
orr n
no
on
n--L
La
attc
ch
hiin
ng
g R
Re
ella
ay
yss
All alarms — alarm 1, alarm 2, and fault — can be jumper programmed to operate as latching or non-latching. If an
alarm is programmed to latch, its corresponding relay and LED indicator, once activated, will stay activated until the
reset button is pressed (assuming, of course, that alarm conditions have cleared).
To program an alarm for latching operation, slide its corresponding switch to the on position. For non-latching opera-
tion slide the switch to the off position. The switch locations are as follows: fault – SW2-2, alarm 1 - SW2-8, and alarm
2 – SW2-5.
Model FL10 Single Channel Flame Detection Control Module PG.4
Alarm Reset/Test
Relay Output
Configuration
Dip Switches
SW2
SW3
Serial ID
Address Setting
Dip Switches
SW2