Detcon FL-10 User Manual

Page 4

background image

Warranty

Two years

Five year f ixed fee service policy

Outputs

Analog 4-20 mA DC

Serial RS-485 Modbus™

Relays

Contacts include common, normally open, and normally closed for three alarms

Resistive load: 5A, 250 VAC; 5A, 30 VDC

Inductive load: 2A, 250 VAC; 2A, 30 VDC

Max. operating current: 5A

2.2 C

ONTROLLER

M

ODELS

The label on the Model FL10 face plate is red. It can be used with any industry standard 4-20 mA f lame detector.

2.3 A

LARM

F

UNCTIONS AND

C

ONTROLLER

C

ONFIGURATION

Model FL10 control modules incorporate several user selectable alarm programming options and general operating

options that are accomplished via dip switches. These options include latching of relays, energized/de-energized relays,

and alarm f iring direction. Reference the f igure below for the applicable dip switch locations and settings.

2

2..3

3..1

1 L

La

attc

ch

hiin

ng

g o

orr n

no

on

n--L

La

attc

ch

hiin

ng

g R

Re

ella

ay

yss

All alarms — alarm 1, alarm 2, and fault — can be jumper programmed to operate as latching or non-latching. If an

alarm is programmed to latch, its corresponding relay and LED indicator, once activated, will stay activated until the

reset button is pressed (assuming, of course, that alarm conditions have cleared).

To program an alarm for latching operation, slide its corresponding switch to the on position. For non-latching opera-

tion slide the switch to the off position. The switch locations are as follows: fault – SW2-2, alarm 1 - SW2-8, and alarm

2 – SW2-5.

Model FL10 Single Channel Flame Detection Control Module PG.4

Alarm Reset/Test

Relay Output

Configuration

Dip Switches

SW2

SW3

Serial ID
Address Setting
Dip Switches

SW2