beautypg.com

Detcon TP-624C User Manual

Page 21

background image

This is the trip point for the second alarm.

Register #

High Byte

Low Byte

40005

Status Bits

Status Bits

High Byte

Bit 7

Not used, always 0

Bit 6

Not used, always 0

Bit 5

Not used, always 0

Bit 4

Not used, always 0

Bit 3

1-Unit is in calibration

0-Normal operation

Bit 2

1-Alarm 2 is ascending

0-Alarm 2 is descending

Bit 1

1-Alarm 2 is normally energized

0-Alarm 2 is normally de-energized

Bit 0

1-Alarm 2 is latching

0-Alarm 2 is non-latching

Low Byte

Bit 7

1-Alarm 2 Relay is energized

0-Alarm 2 Relay is not energized

Bit 6

1-Alarm 1 is ascending

0-Alarm 1 is descending

Bit 5

1-Alarm 1 is normally energized

0-Alarm 1 is normally de-energized

Bit 4

1-Alarm 1 is latching

0-Alarm 1 is non-latching

Bit 3

1-Alarm 1 Relay is energized

0-Alarm 1 Relay is not energized

Bit 2

1-Fault is normally energized

0-Fault is normally de-energized

Bit 1

1-Fault is latching

0-Fault is non-latching

Bit 0

1-Fault Relay is energized

0-Fault Relay is not energized

The following is a typical Master Query for device # 8:

Field Name

HEX

DEC

RTU

Slave Address

08

8

0000 1000

Function

03

3

0000 0011

Start Address Hi

00

0

0000 0000

Start Address Lo

00

0

0000 0000

No. of Registers Hi

00

0

0000 0000

No. of Registers Lo

06

6

0000 0110

CRC

##

#### ####

CRC

##

#### ####

The following is a typical Slave Response from device # 8:

Field Name

HEX

DEC

RTU

Slave Address

08

8

0000 1000

Function

03

3

0000 0011

Byte Count

0C

12

0000 1100

Reg40000 Data Hi

02

2

0000 0010

Reg40000 Data Lo

64

100

0110 0100

Reg40001 Data Hi

00

0

0000 0000

Reg40001 Data Lo

64

100

0110 0100

Reg40002 Data Hi

00

0

0000 0000

Reg40002 Data Lo

07

7

0000 0111

Reg40003 Data Hi

00

0

0000 0000

Reg40003 Data Lo

0A

10

0000 1010

Detcon Model TP-624C Hydrogen Sulfide Sensor PG.21