beautypg.com

Delmhorst Instrument BD-10 User Manual

Page 6

background image

hPorch columns that do not have good drainage and

ventilation where they rest on porch floors

hSiding or any other wood that is in contact with the

ground

hSiding and shingles without sufficient lap so that water

is forced up through cracks by wind pressure

hIce dams

hCondensation of vapor within hollow walls

EIFS (Exterior Insulation & Finish Systems)*

Moisture intrusion problems in EIFS (also know as
synthetic stucco) stem from leaking window frames,
improper use of or lack of sealant, and faulty installation
of flashing.

If you suspect a problem take a visual inspection. Look for
gaps around windows, doors, air conditioning units, light
fixtures, hose bibs, dryer vents and other areas of potential
penetration. Also look for visible signs of water damage. If
you feel a problem exists, use the

BD-10 with a #21-E

electrode. This electrode includes the #608 - (4”) insulated
pins
.

Procedure:

hDrill two 1/4” holes about 3/4” apart at an upward

45˚ angle.

hPush the #21-E Electrode into the holes through the

polystyrene and into the substrate.

hPress read button

!

and read the scale.

*Refer to the wood scale

#

if the sheathing is plywood.

If gypsum sheathing is used, refer to the reference
scale

$

.

5