Installing into the transformer winding, Some guidelines for installation, Lumasense technologies awakening your 6 – LumaSense Technologies LumaSHIELD Controller Installation Guide: Winding Temp. Sensors User Manual
Page 4: Sense

www.lumasenseinc.com
©2013 LumaSense Technologies. All rights reserved.
LumaSense Technologies, Inc., reserves the right to change
the information in this publication at any time.
Americas and Australia
Sales & Service
Santa Clara, CA
Ph: +1 800 631 0176
Fax: +1 408 727 1677
Europe, Middle East, Africa
Sales & Service
Frankfurt, Germany
Ph: +49 69 97373 0
Fax: +49 69 97373 167
India
Sales & Support Center
Mumbai, India
Ph: +91 22 67419203
Fax: +91 22 67419201
China
Sales & Support Center
Shanghai, China
Ph: +86 133 1182 7766
Fax: +86 21 5877 2383
LumaSense Technologies
Awakening Your 6
th
Sense
LumaSHIELD Installation Guide - Winding Temperature Sensor -EN 514-0002-01 Rev. A 10/14/13
Installing into the Transformer Winding
Figure 11 shows the sensor installation schematic into the transformer’s windings.
Some Guidelines for Installation
For a safe and successful installation, always follow these steps during the fiber optic sensors installation:
•
Avoid sharp radius turns with the fiber-optic cable
•
Respect specified minimum bending radius for the sensor and cable : 18 mm for 62.5/125 μm fiber
(25 mm preferable)
•
Avoid tensioning or twisting the fiber-optic cable
•
Avoid pinch points and “scissors” when setting the sensors in place
•
Do not pull on fiber-optic cable to clear tangles; carefully unwind instead
•
Avoid dropping or scraping fiber-optic connectors on hard surfaces
•
Keep the surface of the fiber-optic connector very, very clean
•
Use the supplied fiber optic connector cleaner liberally, before and after each and every connection
Figure 11: Installation location in the transformer’s windings..