American Power Conversion 8000VA User Manual

Page 12

background image

10

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

N

ETWORK

M

ANAGEMENT CARD

,

OPTIONAL

S

MART

S

LOT ACCESSORY CARDS OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

High Bypass Point

+10% of
output voltage
setting

+5%, +10%, +15%,
+20%

Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

Low Bypass Point

-30% of output
voltage setting

-15%, -20%, -25%, -30% Minimum voltage that the UPS

will pass to connected
equipment during internal
bypass operation.

Output Voltage

XLJ models:
200 VAC
XLT models:
208 VAC

XLTW models:

220 VAC
XLI models:
230 VAC

XLJ models:
200 VAC
XLT models:
200, 208, 220, 230,
240 VAC
XLTW models:
200, 208, 230, 240 VAC
XLI models:
200, 208, 220, 230,
240 VAC
*Use the voltage setting
applicable to your region.

Allows the user to select the
UPS output voltage while
on-line.

Output Frequency

Automatic
(50 ± 3 Hz or
60 ± 3 Hz)

50 ± 3 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz

Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.

Number of Battery
Packs

1

Number of Connected
Batteries (four battery
modules per pack)

Defines the number of
connected battery packs for
proper runtime prediction.