American Power Conversion 8000VA User Manual
Page 12
![background image](/manuals/36319/12/background.png)
10
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE
,
N
ETWORK
M
ANAGEMENT CARD
,
OPTIONAL
S
MART
S
LOT ACCESSORY CARDS OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
High Bypass Point
+10% of
output voltage
setting
+5%, +10%, +15%,
+20%
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Low Bypass Point
-30% of output
voltage setting
-15%, -20%, -25%, -30% Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage
XLJ models:
200 VAC
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models:
230 VAC
XLJ models:
200 VAC
XLT models:
200, 208, 220, 230,
240 VAC
XLTW models:
200, 208, 230, 240 VAC
XLI models:
200, 208, 220, 230,
240 VAC
*Use the voltage setting
applicable to your region.
Allows the user to select the
UPS output voltage while
on-line.
Output Frequency
Automatic
(50 ± 3 Hz or
60 ± 3 Hz)
50 ± 3 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of Battery
Packs
1
Number of Connected
Batteries (four battery
modules per pack)
Defines the number of
connected battery packs for
proper runtime prediction.