Where to use check valves and foot valves, Maintenance – Davey HM Series Pressure Systems with Pressure Switch User Manual
Page 5

8
5
Where to use Check Valves
and Foot Valves
A check valve is required for fitting to
installations with flooded or positive suction.
Care should be taken to ensure that it is
correctly installed in the suction line for
installations with flooded or positive suction.
Installations with flooded suction require a
gate valve so water supply can be turned
off for pump removal and servicing.
On installations with a suction lift a good
quality foot valve with strainer is required.
Installations with flooded suction require
a gate or isolating valve so water supply
can be turned off for pump removal and
servicing.
For Automatic Pressure Pumps Installed with a
Mains Pressure Hot Water System
To protect your system from damage
caused by back pressure from hot water
systems. You should always have installed
on the hot water inlet an approved non-
return valve.
DO NOT USE THREAD SEALING COMPOUNDS, HEMP OR PIPE
DOPE!
MAINS
WA
TE
R
Check valve
Abrasive Materials
The pumping of abrasive materials will cause damage to the pressure
system which will then not be covered by the guarantee.
Approved
non-return valve
NOTE: Always ensure hot
water systems are installed in
compliance with manufacturers
recommendations and in accordance
with all local regulations.
Maintenance
The only regular attention your new pressure system requires is to check
the pressure tank’s air charge every 6 months.
This can be checked at the air valve with a tyre gauge. Do not charge tank
to a higher pressure than 14 kPa below cut-in
pressure setting.
To check air pressure in tank:
1.
Switch off pump.
2.
Open outlet nearest to pump to release water pressure.
3.
Remove air valve cap from top of Supercell tank and charge tank to
correct pressure using air pump and check with tyre gauge.
4.
Switch on.
5.
Close outlet.
NOTE:
Your pump is designed to operate as an automatic pressure system.
The pressure tank will require a specific precharge air pressure dependent
upon model.
While your pressure tank may have been precharged in manufacture,
the precharge pressure should be checked upon installation and every
6 months thereafter. Follow the instructions on the tank. As a guide, the
precharge settings are listed below:-
Pressure Settings
Pump Model
Cut Out
Cut In
Tank
kPa
kPa
kPa
HM270-19P
300
200
180
HM60-06P
HM90-08P
400
250
230
HM160-15P
HM270-25P
HM60-08P
HM90-11P
500
300
280
HM160-19P
HM60-10P
620
350
330
HM90-13P
Note: The above are standard settings which may be adjusted according
to site conditions. Any adjustments should only be made by a suitably
qualified and experienced person.