Installation steps, Notice – Burcam 300828BUP 1/3HP SUB SUMP SYSTEM 115V/12V VERT/MEC SWITCH User Manual
Page 5
INSTALLATION STEPS
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
STEP 7
STEP 8
STEP 9
STEP 10
STEP 11
Installation of this unit may take several hours. Before disabling your main pump, have
ready appropriate means of evacuating the sump.
Turn off power to main pump.
Check valve : If you install your emergency 12 V pump using the same
discharge pipe of your main 115V pump, a check valve is required
between the T or Y connection and both pumps. We supply a check
valve with this emergengy pump. Be sure your main 115V pump is
equipped with a check valve (see picture 1). These check valves are
required to prevent backflow to the sump pit.
We strongly suggest to run your discharge pipe with 1 1/2” rigid PVC piping.
The emergency pump must be installed at 45
0
angle (see picture 2) to
prevent airlock into the pump body.
Screw the supplied adaptors and check valve to the pump discharge
using
TEFLON
tape (see picture 3).
Glue a 45
0
fitting to the check valve to maintain the pump in same
position as per picture 2 and 3.
Mesure and cut a discharge pipe so that back-up pump is 4” to 8” above
the bottom of the sump pit.
Connect the discharge pipe of back-up pump to the discharge pipe of the
main pump using a Y and a 45
0
fitting as per picture 4.
Be sure all connections are well glued.
Attach the float switch to the back-up pump discharge pipe using the
enclosed tie-wrap, as per picture 4. The standby pump’s float switch
should be installed so that it will not activate until standby pump’s inlet is
under water. Make sure power wires do not interfere with float switch or
pump inlet.
Place battery box within 3 feet of the sump and install a 115V AC
separately fused outlet within 5 feet of the control box. The electrical
outlet must be protected by a ground fault circuit interrupter (GFCI).
The area must be also clean, dry and well ventilated.
Fix the control box to the battery box.
Plug the float switch, pump and charger to the appropriate connector as
per picture 5. Test pump operation by filling the sump with water while the
main pump is unplugged. If the pump operates properly, plug the charger
into the GFCI protected outlet to keep the battery charged.
Protect electrical cord from sharp objects, hot surfaces, oil and chemicals.
Avoid kinking the cord and replace damaged components immediately.
Picture #1
Picture #2
Picture #3
Picture #4
NOTICE
BATTERY PUMP
STEP 12
STEP 13
STEP 14
Picture #5
The control box contains a multi-colored indicator lights.
1-The green charged light indicates a full charge.
2-The red battery low light indicates a low voltage.
3-The yellow charging light indicates a charge function in progress.
4-The red reversed light indicates a reverse connection on the batterie cables.
5-The alarm selector can be put in on or off position as per your choice. If the
alarm turns on, the red alarm light will turn on.
6-To test the pump operation, push the pump test button.
7-To stop the alarm, if in on position, push the reset button.
Note that if activated, the alarm will turn on as soon as the pump turns on. This will warn you
that the pump turned on due to a power failure or a primary pump failure.
5