Performance review - light derating factor, Caution – STI SS-2406EX User Manual
Page 2

• This enclosure is rated to protect signaling appliances indoors and in areas of indirect weather
exposure. The cover may be used outdoors only with devices also suitable for outdoor use.
• When covering fire-signaling appliances with this enclosure, some light and sound loss
occurs. Please follow these guidelines listed during installation.
• Voice speaker appliance: No spacing adjustment is required for 0.5W, 1.0W and 2.0W
appliances.
• Refer to the appliance manufacturer's candela rating. Multiply this number by the light loss
value from the chart below to determine the new candela rating. Use this number and refer
to the notification layout table of NFPA 72 for proper device locations.
• The use of this cover on audible devices decreases the sound output by 6dB(A). Actual sound
level output should be checked after installation to determine if adequate sound levels exist.
Refer to the notification layout table of NFPA 72 for proper device locations.
Performance Review - LIGHT DERATING FACTOR
ADT SECURITY
ADTG1-V SERIES
40%
34%
HONEYWELL
XLS202 SERIES
40%
34%
AMSECO
SL24W-153075
22%
37%
HONEYWELL
XLSG1-HV SERIES
40%
34%
AMSECO – COLORED LENSES
SL24W-153075 A, B, G, OR R
47%
26%
HONEYWELL
XLSG1-HOV SERIES
40%
34%
AMSECO – COLORED LENSES
SL24C-3075110 A, B, G, OR R
47%
26%
MIRCOM
FS-240
47%
26%
AMSECO – COLORED LENSES
CSL24W-A, B, G, OR R
47%
26%
MIRCOM
MS SERIES
43%
45%
AMSECO – COLORED LENSES
CSL24C-A, B, G, OR R
47%
26%
MIRCOM
MG1-V SERIES
40%
34%
DETECTION SYSTEMS
GES24 SERIES
-
31%
MIRCOM
MG1-HV SERIES
40%
34%
DETECTION SYSTEMS
GES24-15/75
-
-
MIRCOM
MG1-HOV SERIES
40%
34%
EST / EDWARDS
2440S SERIES
43%
45%
MIRTONE
MG1-V SERIES
43%
45%
EST / EDWARDS
202 SERIES
43%
45%
NATIONAL TIME & SIGNAL
GES24 SERIES
-
31%
EST / EDWARDS
G1-V SERIES
40%
34%
NATIONAL TIME & SIGNAL
GES24-15/75
-
-
EST / EDWARDS
G1-HV SERIES
40%
34%
POTTER ELECTRIC
AS-24-153075R
47%
26%
EST / EDWARDS
G1-HOV SERIES
40%
34%
POTTER ELECTRIC
AS-24-153075W
47%
26%
EST / EDWARDS
EG1-V SERIES
40%
34%
SECUTRON
GES24 SERIES
-
31%
EST / EDWARDS
EG1-HV SERIES
40%
34%
SECUTRON
GES24-15/75
-
-
EST / EDWARDS
EG1-HOV SERIES
40%
34%
SIEMENS
202- SERIES
43%
45%
FARADAY LLC
2700
-
57%
SIEMENS
G1-V SERIES
40%
34%
GENTEX
GES24 SERIES
-
31%
SIEMENS
U-MCS SERIES
-
-
GENTEX
GES24-15/75
-
-
SYSTEM SENSOR
SS24110ADA
46%
37%
HARRINGTON SIGNAL
GES24 SERIES
-
31%
SYSTEM SENSOR
P2, PC2, P4, PC4, SX, SC
53%
61%
HARRINGTON SIGNAL
GES24-15/75
-
-
WHEELOCK
RSS-24MCW
-
-
HONEYWELL
XLSG1-V SERIES
43%
45%
ZITON PTY LTD
ZG1-V SERIES
40%
34%
MANUFACTURER
SERIES
STI-1210
STI-1221/1221A4X
MANUFACTURER
SERIES
STI-1210
STI-1221/1221A4X
STI-1210 Series Sound Derating Factor
System Sensor P2, PC2, P4, PC4, SX, SC series models: 6.7 dBA
General: 6 dBA
STI Generic Light Loss Value
STI-1210 Series: 53%; STI-1221 Series: 61%
SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • INFO @ www.sti-usa.com
UL INSTALLATION REQUIREMENTS
STI-1210 / STI-1221 SERIES
04/2006
CAUTION: