PULS QS40.241 User Manual
Page 6
1-Phase Power Supply Instruction Manual
Bedienungsanleitung für 1-Phasen Stromversorgungen
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperature of:
60°C for ambient temperatures up to 45°C,
75°C for ambient temperatures up to 60°C and
90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter
the terminal connection! Ferrules are allowed.
Input Output
Signals
Solid
wire
0.5-6mm
2
0.5-16mm
2
0.15-1.5mm
2
Stranded
wire
0.5-4mm
2
0.5-10mm
2
0.15-1.5mm
2n
American wire gauge
AWG 20-10
AWG 22-8
AWG 26-14
Max.
wire
diameter 2.8mm
5.2mm
1.5mm
(including
ferrules)
Wire stripping length
7mm / 0.28inch
12mm / 0.5inch
7mm / 0.28inch
Tightening torque
1Nm / 9lb.inch
2.3Nm / 20.5lb.inch
Spring-clamp terminal
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für:
60°C bei einer Umgebungstemperatur bis zu 45°C,
75°C bei einer Umgebungstemperatur bis zu 60°C und
90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.
Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass
keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
Eingang Ausgang Signale
Starrdraht
0,5-6mm
2
0,5-16mm
2
0,15-1,5mm
2
Litze
0,5-4mm
2
0,5-10mm
2
0,15-1,5mm
2
AWG
AWG 20-10
AWG 22-8
AWG 26-14
Max.
Drahtdurchmesser
2,8mm
5,2mm
1,5mm
(inklusive
Aderendhülsen)
Abisolierlänge
7mm / 0,28inch
12mm / 0,5inch
7mm / 0,28inch
Anzugsdrehmoment
1Nm / 9lb.inch
2.3Nm / 20,5lb.inch
Federkraftklemme
Indicators, LEDs
Overload LED
DC-OK LED
DC-OK Contact
Normal mode
OFF
ON
Closed
During BonusPower
®
OFF
ON
Closed
Overload (Hiccup mode)
flashing
OFF
Open
Output short circuit
flashing
OFF
Open
Temperature Shut-down
flashing
OFF
Open
Active Shut-down input
flashing
OFF
Open
Anzeigelampen
Overload LED
DC-OK LED
DC-OK Contact
Normalbetrieb AUS
EIN
geschlossen
Während BonusPower
®
AUS
EIN
geschlossen
Überlast (Hiccup- Modus) blinken
AUS
offen
Ausgangskurzschluss
blinken AUS
offen
Temperaturabschaltung blinken
AUS
offen
Aktiver „shut-down“ Eingang
blinken
AUS
offen
Fig. 8 / Bild 8
QS40.241, QS40.361, QS40.481; Functional Diagram / Funktionsschaltbild
Fig. 9 / Bild 9
QS40.244, QS40.484; Functional Diagram / Funktionsschaltbild
+
+
-
-
V
OUT
DC-ok
Contact
Output
Over-
Voltage
Protection
Bridgeless
PFC
Converter
Input Fuse
Input Filter
Inrush Limiter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
LED
DC-ok
LED
N
L
Single /
Parallel
Shut-down
Input &
Remote
Control
Shut-
down
13
14
15
16
Event Datalogger
+
+
-
-
V
OUT
DC-ok
Contact
Output
Over-
Voltage
Protection
PFC
Converter
Input Fuse
Input Filter
Input Rectifier
Inrush Limiter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Overload
LED
DC-ok
LED
N
L
Single /
Parallel
Shut-
down
13
14
15
16
Event Datalogger
Shut-down
Input &
Remote
Control
Fig. 10 / Bild 10
QS40.241, QS40.361, QS40.481; Dimensions / Abmessungen
Fig. 11 / Bild 11
QS40.244, QS40.484; Dimensions / Abmessungen
PU-384.010.00-10A