Introduction

About this unit

The American Power Conversion (APC

®

) SUA48XLBPexternal battery pack connects to the APC

Smart-UPS

®

. Together these units provide extended protection for electronic equipment from utility power

blackouts, brownouts, sags and surges. The UPS and the external battery pack together provide continuous

power from the batteries until utility power returns to safe levels or the batteries are fully discharged.

Unpack

Read the Safety Guide before installing the unit.
Inspect the unit upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:

Specifications

NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label

is located on the chassis under the front bezel.

•External battery pack
•Front bezel
•Literature kit containing:

– Eight ornamental screws for securing the unit in the

rack

– Eight 5/16 in (.8 cm) pan-head screws for attaching

cleats to the chassis rails

(required for four post rack only)

– Eight 5/8 in (1.6 cm) pan-head screws for attaching

rack-mount brackets to the unit

– Eight snap-on speed nuts

– Two cleats (required for four post rack only)
– Two rack-mount brackets
– Product documentation
– Smart-UPS

®

User Manuals CD

– Safety information
– Warranty information

Temperature

Operating

Storage

32

°

to 104

°

F (0

°

to 40

°

C)

5

°

to 86

°

F (-15

°

to 30

°

C) charge the batteries every six months

86

°

to 113

°

F (30

°

to 45

°

C) charge the batteries every three months

This unit is intended for indoor use

only. Select a location sturdy enough

to handle the weight.
Do not operate the unit where there

is excessive dust or the temperature

or humidity are outside the specified

limits.
Environmental factors impact battery

life. High temperatures, poor utility

power, and frequent, short duration

discharges will shorten battery life.

Maximum

Elevation

Operating

Storage

10,000 ft (3,000 m)
50,000 ft (15,240 m)

Humidity

0 to 95% relative humidity, non-condensing

Weight

150 lbs (68 kg) with battery module
40 lbs (18 kg) without battery module
27 lbs (12 kg) each battery module

150 lbs (68 kg)

Maximum Number of External Battery Packs Supported by the

Smart-UPS XL

10