beautypg.com

Sterling QVSF User Manual

Page 25

background image

1. Check and tighten all wiring

connections per diagrams. Thermostat

wires tagged “W” and “G” must be

connected together (unless special

thermostats are used; if so, see

thermostat wiring diagram). See

electrical

connections.

2. Replace

motor.

3. Check for 24V across “H” terminals

on fan time delay switch. If 24V is

present, jumper terminals numbered 2

and 4. If motor runs, the fan switch is

defective and must be replaced. If 24V is

not present, check wiring per diagrams.

1. Be sure fan switch heater terminals

are connected per diagrams.

2. Replace fan switch.
3. Check motor amps against motor

name plate rating, check voltage,

replace fan motor if defective.

4. Refer to label on motor.

1. Check all wiring.

2. Refer to H or N symptoms.

3. Replace fan switch.

1. Refer

to

“Operation”.

2. This is especially true when the

heated space is enlarged. Have the

heat loss calculated and compare to

the heater output (80% of input). Your

gas supplier or installer can furnish

this information. If heater is under

sized, add additional heaters.

3. Replace

thermostat.

4. There should be NO ducts attached to

the front of this heater. Check air

movement through heat exchanger.

Check voltage to fan motor. Clean fan

blade and heat exchanger and oil fan

motor.

1. Replace

thermostat.

2. Check wiring per diagrams; Check

operation at valve. Look for short

(such as staples piercing thermostat

wiring), and correct; Replace gas

valve; Refer to “Operation”.

1. Be sure fan switch heater terminals

are connected per diagrams.

1. Refer

to

“Operation”.

2. Check motor voltage with fan running.

Should be 115 volts AC.

3. Refer

to

“Operation”.

1. Close thermostat contacts.
2. Check for 24V across 24V terminals

of

S8600.

3. Set gap to 0.1".
4. Replace pilot assembly.

25

Power Vented Propellers Troubleshooting Guide

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

1. Loose

wiring.

2. Defective motor overload protector or

defective

motor.

3. Defective fan switch.

1. Fan switch heater element improperly

wired.

2. Defective fan switch.
3. Motor overload protector cycling on

and

off.

4. Motor not properly oiled.

1. Improperly wired fan control.
2. Main burners not lighting while

thermostat calls for heat.

3. Defective fan switch.

1. Incorrect gas input.

2. Heater

undersized.

3. Thermostat

malfunction.

4. Heater cycling on limit control.

1. Thermostat

malfunction.

2. Heater runs continuously.

1. Fan switch heater element improperly

wired.

1. Incorrect manifold pressure or input.

2. Voltage to unit too high.

3. Air through put too high.

1. Thermostat not calling for heat.
2. No low voltage.

3. Spark gap closed or too wide.
4. Broken or cracked ceramic on spark

electrode.

O. Fan will not run.

P. Fan motor turns on and off

while burner is operating.

Q. Fan motor will not stop.

R. Not enough heat.

T. Too much heat.

U. Cold air is delivered on start

up.

V. Cold air is delivered during

heater

operation.

W.

No

Spark.