Venting - general guidelines – Sterling GG User Manual
Page 3

3
VENTING - GENERAL GUIDELINES
Venting Categories
Non
Condensing
Condensing
Negative
Vent
I
II
Pressure
Positive
Vent
III IV
Pressure
The following guidelines apply to all categories to follow.
Table 1
Do not damper or add heat recovery devices to the fl ue
piping. Failure to open such a damper prior to operating
the gas unit heater will result in the spillage of fl ue gas
into the occupied space.
Avoid installing units in areas under negative pressure.
When required, a flue vent fan should be installed in
accordance with the instructions included with the fan.
Vent connectors serving Category
I
and Category
II
heaters shall not be connected into any portion of
mechanical draft systems operating under positive vent
pressure.
Maintain 1-inch (25.4mm) clearance between the vent
pipe and combustible materials.
ANSI now organizes vented appliances into four
categories.
Category
I
Includes non-condensing appliances with negative vent
pressure, like the traditional atmospheric unit heater.
Category
II
Groups condensing appliances with negative vent
pressure.
Category
III
Appliances are non-condensing and operate with a
positive vent pressure.
Category
IV
Covers condensing appliances with positive vent
pressure.
NOTICE: Category
II
and
IV
do not apply to equip-
ment specifi ed within this manual.
Vent Systems
Termination Clearance Requirements
Structure/Object
Minimum Clearances
for Termination Locations
USA
CANADA
Door, window, or gravity vent
inlet; combustion air inlet for
other appliances
9 in. for 10,000
to 50,000 BTU/Hr
input; 12 in. for
input exceeding
50,000 BTU/Hr.
9 in. (230mm)
for 10,000 to
50,000 BTU/Hr
input; 12 in. (305mm)
for input exceeding
50,000 BTU/Hr.
Forced air inlet within 10 ft.
3 ft. above
6 ft. (1.8m)
Adjoining building or parapet
10 ft.
10 ft. (3.04m)
Adjacent public walkways
7 ft. above
grade
7 ft. (2.1m) above
grade
Electric, gas meters
& regulators
4 ft. horizontal
3 ft. (0.9m)
horizontally from
meter/regulator
assembly. 6 ft. (1.8m),
any direction, from a
gas service regulator
vent outlet
Above grade level*
1 ft.
1 ft. (0.3m)
*Minimum above snow depth, or per local code, whichever is greater.