Sterling TD User Manual
Page 2

2
VENTING FOR POWER VENTED DUCT FURNACES (CATEGORY III)
GENERAL GUIDELINES
All duct furnaces must be vented! All venting installations shall be in accordance with the latest edition of Part 
7, Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54), or applicable provisions of local 
building codes for power vented units. Refer to Figures 3a, 3b, 4a, 4b, 5a, and 5b. For installations in Canada, see 
page 3. 
CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts, or
any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all times! Failure to 
heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, 
inappropriate tiredness, or fl u-like symptoms).
NOTICE: All vertical and horizontal venting arrange-
ments for the Tubular Duct Furnace are Category III 
venting.
ANSI now organizes vented appliances into four 
categories.
Venting Categories
Non
Condensing
Condensing
Negative
Vent Pressure
I
II
Positive
Vent Pressure
III
IV
Category I
Includes non-condensing appliances with negative vent 
pressure, like the traditional atmospheric unit heater.
Category II
Groups condensing appliances with negative vent 
pressure.
Category III
Appliances are non-condensing and operate with a 
positive vent pressure.
Category IV
Covers condensing appliances with positive vent 
pressure.
Do not damper or add heat recovery devices to the fl ue 
piping. Failure to open such a damper prior to operating 
gas unit will result in the spillage of fl ue gas into the 
occupied space.
Vent pipe material must be in compliance with UL 1738 
for installations in the United States, and UL S636 for 
installations in Canada.
Refer to Table 1 for vent termination clearance 
requirements.
Through the wall vents for these appliances shall NOT 
terminate over public walkways, or over an area where 
condensate or vapor could create a nuisance or hazard 
or could be detrimental to the operation of regulators, 
relief valves, or other equipment.
The vent pipe equivalent length must be 5 feet (1.5m) 
minimum and must not exceed 50 feet (15.2m). 
Equivalent length is the total length of straight 
sections PLUS 10 feet (3.05m) for each 90 degree 
elbow, and 4 feet (1.22M) for each 45 degree elbow.
Maintain 6 inch (152mm) between vent pipe and 
combustible materials. A minimum of 12 inch (305mm) 
of straight pipe is required from the venter outlet before 
installing an elbow in the vent system. An elbow should 
never be attached directly to the venter!
Never use a pipe of a diameter other
than that specifi ed in Table 1! Never use PVC or other 
nonmetallic pipe for venting! To do so may result in 
serious damage to the unit, severe personal injury, 
or death.
Any run of single wall vent pipe exposed to cold air or 
passing through an unheated space must be insulated 
with insulation suitable to 550°F (288°C).
The vent system must be installed to prevent collection 
of condensate. Vertical vent pipes should be equipped 
with condensate drains. Pitch horizontal pipes down-
ward 1/4 inch per foot (21mm/m) toward outlet for 
condensate drainage. 
Horizontal portions of the venting system shall be 
supported at maximum intervals of 4 feet (1.2m) to 
prevent sagging. In Canada, support at a maximum 
of 3 feet (1m) intervals.
Each unit must have an individual vent pipe and 
vent terminal per furnace section! Each unit MUST 
NOT be connected to other vent systems or to a 
chimney.
