beautypg.com

External wiring, Setting parameters, List of parameters – Yokogawa JUXTA FH5V Isolator (with Square Root Extractor) User Manual

Page 3: Warning

background image

3

IM 77J08H05-01E 1st Edition

2008.01.15-00

3. EXTERNAL WIRING

WARNING

Be sure to turn OFF the power supply before wiring to
avoid the risk of electric shock. Use a tester or similar
device to ensure that no power is being supplied to a
cable to be connected

.

M4 screw terminals are provided for the connection of external
signals. Attach a crimp-on lug to each wire for connection to the
terminals.
●Recommended cables: A nominal cross-sectional area of 0.5
mm2 or thicker for signal cables, and that of 1.25 mm2 or thicker
for power cables.

Wiring Diagram

2

3

4

5

6

7

6
7

4
5

Output

Power Supply

Input

2
3

+

+

+

NOTE

●Do not connect anything to the terminals that are not

used in the wiring diagram. Otherwise it may cause
the malfunction or damage.

●The power line and input/output signal lines should

be installed away from noise-generating sources.
Otherwise accuracy cannot be guaranteed.

●Adhere strictly to the specifications to avoid

overheating or damage. Before turning on the power,
ensure the following:
(a) Power supply voltage and input signal value

applied to the product should meet the required
specifications.

(b) The external wiring to the terminals are as

specifications.

●Do not operate the product in the presence of

flammable or explosive gases or vapors.

●The product is sensitive to static electricity; exercise

care in handling. Before you operate the product,
touch a nearby metal part to discharge static
electricity.

Power Supply and Isolation

Power supply voltage: 24 V DC ±10% (percentage ripple: less

than 5% p-p)

Current consumption: FH5A 70 mA, FH5V 50 mA
Insulation resistance: 100 MΩ at 500 V DC between input and

output, output and power supply, and input and
power supply.

Withstand voltage: 1500 V AC/min. between input and (output

and power supply)

500 V AC/min. between output and power supply

4. SETTING PARAMETERS

The parameters are set as you specified in your order. Refer
to the following to change the default settings.

Set the parameters using a PC (VJ77 Parameter Setting Tool)
or the Handy Terminal. Refer to "5. List of Parameters" in this
manual and the User’s Manual for VJ77 PC-based Parameters
Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200
Handy Terminal (IM JF81-02E). Parameters are shown in
brackets "[ ]".

Connection of Setting Tools

VJ77 Dedicated adapter

[Provided with VJ77]

PC with VJ77 installed

Dedicated cable

[Provided with VJ77]

*Be sure to use the VJ77 of version R1.05 or later.

JHT200

Handy Terminal

JUXTA communication cable

3 pin connector (F9182ED)

[Provided with VJ77 and JHT200]

Setting Low Cut Point

Set the low cut point in

[B07: LOW CUT].

Setting range: 0.3 to 100% of the input range (setting
resolution 0.1%)

Output=Input

Low cut point

Input

Hysteresis
(fixed at approx. 0.2%)

Output

5. LIST OF PARAMETERS

Parameter Display

Items

A

DISPLAY

Display

A01

INPUT

Input value

A02

OUTPUT

Output value

A03

STATUS

Status (*1)

A04

REV NO

Revision number

B

SET

Setting

B01

TAG NO.1

Tag number 1

B02

TAG NO.2

Tag number 2

B03

COMMENT1

Comment 1

B04

COMMENT2

Comment 2

B07

LOW CUT

Low cut point

C

ADJUST

Adjustment

C01 OUT 0%

Output 0% adjustment

C02 OUT 100%

Output 100% adjustment

C04 ZERO ADJ

Input zero adjustment

C05 SPAN ADJ

Input span adjustment

*1: This “STATUS” is for the customer’s engineer to check the history.

This manual is related to the following products: