External wiring, Setting parameters, List of parameters – Yokogawa JUXTA FH5V Isolator (with Square Root Extractor) User Manual
Page 3: Warning
3
IM 77J08H05-01E 1st Edition
2008.01.15-00
3. EXTERNAL WIRING
WARNING
Be sure to turn OFF the power supply before wiring to
avoid the risk of electric shock. Use a tester or similar
device to ensure that no power is being supplied to a
cable to be connected
.
M4 screw terminals are provided for the connection of external
signals. Attach a crimp-on lug to each wire for connection to the
terminals.
●Recommended cables: A nominal cross-sectional area of 0.5
mm2 or thicker for signal cables, and that of 1.25 mm2 or thicker
for power cables.
Wiring Diagram
2
3
4
5
6
7
6
7
4
5
Output
Power Supply
Input
2
3
+
–
+
–
+
–
NOTE
●Do not connect anything to the terminals that are not
used in the wiring diagram. Otherwise it may cause
the malfunction or damage.
●The power line and input/output signal lines should
be installed away from noise-generating sources.
Otherwise accuracy cannot be guaranteed.
●Adhere strictly to the specifications to avoid
overheating or damage. Before turning on the power,
ensure the following:
(a) Power supply voltage and input signal value
applied to the product should meet the required
specifications.
(b) The external wiring to the terminals are as
specifications.
●Do not operate the product in the presence of
flammable or explosive gases or vapors.
●The product is sensitive to static electricity; exercise
care in handling. Before you operate the product,
touch a nearby metal part to discharge static
electricity.
Power Supply and Isolation
Power supply voltage: 24 V DC ±10% (percentage ripple: less
than 5% p-p)
Current consumption: FH5A 70 mA, FH5V 50 mA
Insulation resistance: 100 MΩ at 500 V DC between input and
output, output and power supply, and input and
power supply.
Withstand voltage: 1500 V AC/min. between input and (output
and power supply)
500 V AC/min. between output and power supply
4. SETTING PARAMETERS
The parameters are set as you specified in your order. Refer
to the following to change the default settings.
Set the parameters using a PC (VJ77 Parameter Setting Tool)
or the Handy Terminal. Refer to "5. List of Parameters" in this
manual and the User’s Manual for VJ77 PC-based Parameters
Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200
Handy Terminal (IM JF81-02E). Parameters are shown in
brackets "[ ]".
Connection of Setting Tools
VJ77 Dedicated adapter
[Provided with VJ77]
PC with VJ77 installed
Dedicated cable
[Provided with VJ77]
*Be sure to use the VJ77 of version R1.05 or later.
JHT200
Handy Terminal
JUXTA communication cable
3 pin connector (F9182ED)
[Provided with VJ77 and JHT200]
Setting Low Cut Point
Set the low cut point in
[B07: LOW CUT].
Setting range: 0.3 to 100% of the input range (setting
resolution 0.1%)
Output=Input
Low cut point
Input
Hysteresis
(fixed at approx. 0.2%)
Output
5. LIST OF PARAMETERS
Parameter Display
Items
A
DISPLAY
Display
A01
INPUT
Input value
A02
OUTPUT
Output value
A03
STATUS
Status (*1)
A04
REV NO
Revision number
B
SET
Setting
B01
TAG NO.1
Tag number 1
B02
TAG NO.2
Tag number 2
B03
COMMENT1
Comment 1
B04
COMMENT2
Comment 2
B07
LOW CUT
Low cut point
C
ADJUST
Adjustment
C01 OUT 0%
Output 0% adjustment
C02 OUT 100%
Output 100% adjustment
C04 ZERO ADJ
Input zero adjustment
C05 SPAN ADJ
Input span adjustment
*1: This “STATUS” is for the customer’s engineer to check the history.