Yokogawa JUXTA FA5V Distributor (with Square Root Extractor) User Manual
User's manual, Checking product specifications and package, General

User's
Manual
Thank you for purchasing the JUXTA Signal Conditioner.
Please read through this manual before use for correct handling.
Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan
Phone: +81-422-52-7179 Facsimile: +81-422-52-6619
IM 77J08A05-01E
1st Edition Jan.2008 (YK)
CAUTIONARY NOTES FOR SAFE USE OF THE
PRODUCT
This User’s Manual should be carefully read before installing and
operating
the product. Please keep this User's Manual for future reference.
The following symbol is used on the product and in this manual to
ensure safe usage.
This symbol is displayed on the product when it is
necessary to refer to the User's Manual for information
on personal and instrument safety. This symbol is
displayed in the User's Manual to indicate precautions
to avoid danger to the operator, such as an electric
shock.
The following symbols are used only in this manual.
NOTE
Draws attention to essential information for
understanding the operations and/or functions of the
product.
CHECKING PRODUCT SPECIFICATIONS AND
PACKAGE
(1) Checking the Model and Product Specifications
Check that the model and specifications indicated on the
nameplate
attached to the main unit are as ordered.
(2) Packaged Items
Check that the package contains the following items:
FA5A or FA5V: 1
Mounting block: 2
Tag number label : 1
Mounting screw (M4 x 0.7): 2
User’s Manual (this manual : IM 77J08A05-01E)
GENERAL
The FA5A/FA5V is a compact, front terminal connection type
distributor with square root extractor, is used in combination with
a two-wire transmitter to convert the differential pressure flow
signal into a linearized signal proportional to the flow.
Low cut point setting, zero/span adjustment, and I/O monitoring
can be made using optional Parameter Setting Tool (VJ77) or
Handy Terminal (JHT200).
MODEL AND SUFFIX CODES
Model
Suffix codes Description
FA5A
- *C Distributor (with Square Root Extractor)
FA5V
Input
-A
4 to 20 mA DC
Transmitter power supply 25.25 ± 0.25V DC
Output
A
4 to 20 mA DC
FA5A
B
2 to 10 mA DC
C
1 to 5 mA DC
D
0 to 20 mA DC
E
0 to 16 mA DC
F
0 to 10 mA DC
G
0 to 1 mA DC
Z
(Custom order) DC current signal
1
0 to 10 mV DC
FA5V
2
0 to 100 mV DC
3
0 to 1 V DC
4
0 to 10 V DC
5
0 to 5 V DC
6
1 to 5 V DC
7
-10 to 10 V DC
0
(Custom order) DC voltage signal
Style code
*C Style C
Models FA5A, FA5V
Distributor
(with Square Root Extractor)