Smart hart, Loop interface and monitor – Yokogawa HIMHART User Manual
Page 8
HIM
8
The Interface Solution Experts
Smart HART
Loop
Interface and Monitor
Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal
EMC (Electromagnetic Compatibility) directives
(EN55011, EN 50082-1, EN50082-2, etc.). Consult the
factory for the most current information on products
that have been CE certified.
Recommended Ground Wiring Practices
Moore Industries recommends the following ground
wiring practices:
• Any Moore Industries product in a metal
case or housing should be grounded.
• The protective earth conductor must be
connected to a system safety earth ground
before making any other connections.
• All input signals to, and output signals
from, Moore Industries’ products should be
wired using a shielded, twisted pair
technique. Shields are to be connected to an
earth or safety ground at the unit itself.
• The maximum length of unshielded input
and output signal wiring should be 2 inches.
Power Sourcing Parameters for General
Locations, Intrinsically Safe, and
Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H
(all models), the input terminals must be
connected to and/or supplied from a certified
energy limiting Class 2 or a Separate Extra Low
Voltage (S.E.L.V.) power supply separated from
all mains by double/reinforced insulation.
READY
INPUT
TRIP 2
TRIP 1
COM
0
ADDR
COMMON
NC (normally closed)
NO (normally open)
4-20mA
DCS
Sensor
Input
NO
NC
DC
GND
–
+
24Vdc
Power
Source
DCC
R must be > 250 and <1100 Ohms
R
HART Multivariable
Field Instrument
(Temperature,
Pressure, Level
and Flow)
Analog Output tied to
Any Process Variable
Event Recorder
HART Communicator
can be connected
anywhere on the loop
COM
+IN
+TX
–IN
1
2
3
4
5
6
7
8
9
0
.
—
➤
➤
➤
➤
➤
➤
➤