Smart HART

Loop

Interface and Monitor

Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal

EMC (Electromagnetic Compatibility) directives
(EN55011, EN 50082-1, EN50082-2, etc.). Consult the
factory for the most current information on products
that have been CE certified.

Recommended Ground Wiring Practices
Moore Industries recommends the following ground
wiring practices:

• Any Moore Industries product in a metal
case or housing should be grounded.

• The protective earth conductor must be
connected to a system safety earth ground
before making any other connections.

• All input signals to, and output signals
from, Moore Industries’ products should be
wired using a shielded, twisted pair
technique. Shields are to be connected to an
earth or safety ground at the unit itself.

• The maximum length of unshielded input
and output signal wiring should be 2 inches.

Power Sourcing Parameters for General
Locations, Intrinsically Safe, and
Non-Incendive/Type N applications
In accordance with IEC 1010.1 Annex H
(all models), the input terminals must be
connected to and/or supplied from a certified
energy limiting Class 2 or a Separate Extra Low
Voltage (S.E.L.V.) power supply separated from
all mains by double/reinforced insulation.

READY

INPUT

TRIP 2

TRIP 1

COM

0

ADDR

COMMON

NC (normally closed)

NO (normally open)

4-20mA

DCS

Sensor

Input

NO

NC

DC

GND

+

24Vdc
Power

Source

DCC

R must be > 250 and <1100 Ohms

R

HART Multivariable

Field Instrument

(Temperature,

Pressure, Level

and Flow)

Analog Output tied to
Any Process Variable

Event Recorder

HART Communicator
can be connected
anywhere on the loop

COM

+IN

+TX

–IN

1

2

3

4

5

6

7

8

9

0

.