3.5 EXAMPLE
A vortex flowmeter has a maximum output of 20.538 litres/min at 20mA. It is
required to display the flowrate in litres/min with 1 decimal point and the total in
litres with no decimals. High and low alarms are required at 18 l/m and 2 l/m
respectively. The instrument is then programmed as follows.
CAL00
0
No Pulse Output
CAL01
00020
Span (Whole Numbers)
CAL02
5380
Span (Decimals)
03
0.05
Cutoff Point as a fraction of Span
04
1
Rate decimal position
05
1
Timebase
06
01
Filter disabled
07
0
Total decimal position
08
0001
Total Conversion (set to 1.0000)
09
0000
Total Conversion (decimals)
10
00002
Low Alarm
11
0000
Low Alarm
12
00018
High Alarm
13
0000
High Alarm
14
0
Linear Input
15
xxxx Accumulated Totals
SOFT
202A1.11
Software Version
Programming 19