Yokogawa ADMAG CA User Manual
Page 9
IM 1E8B0-01E
13-2
(4) Maintenance and Repair
The instrument modification or parts replacement by other than authorized
representative of Yokogawa Electric Corporation is prohibited and will void
the approval of Factory Mutual Research Corporation.
HAZARDOUS LOCATIONS
Magnetic Flow Converter
Conduit
Sealing Fitting
18"(457mm) Max.
13.2 CSA (Only for sizes 15 to 100 mm(0.5 to 4 in))
(1) Technical Data
Optional code /CF11
Applicable Standard:
CSA Standard C22.2
No.0, No.0.4, No.0.5, No.25, No.30, No.94, No.61010-1
Certificate:
1500865
Explosion proof for Class I, Groups B, C and D; Class II, Groups E, F and G; Class III
Temp. Code: T6 T5 T4
Process Temp.: 70 85 120
°C
Ambient Temp.: –20
°C to +50°C (–4 to 122°F)
Maximum power supply voltage: 240 Vac/ 120 Vdc
Enclosure: TYPE 4X
(2) Installation
All wiring shall comply with Canadian Electrical Code Part I and Local
Electrical Codes.
In hazardous location, wiring shall be in conduit as shown in the figure.
CAUTION :
SEAL ALL CONDUITS WITHN 50cm OF THE ENCLOSURE’
UN SCELLEMENT DOIT ÉTRE INSTALLÉ À MOINS DE
50cm DU BOÎTIER.