7. Troubleshooting

Problem

Possible Cause

Solution

Constant Alarm on

one or more unused

zones.

Unused zones not

jumpered.

Connect a wire

between the COM

and NC terminals of

all unused zones (see

section 4).

Constant low tem-

perature and humid-

ity readings.

12 Vdc supply (pin

1) shorted to ground

or overloaded.

Correct short

circuit—examine all

sensors that use the

12 Vdc power

supply.

No communication
with UPS or acces-

sories.

Measure-UPS II has

failed.

If removing Mea-

sure-UPS II from the

host cures the com-

munication problem

for other accessories,

call technical sup-

port at the number

on the back cover of

this manual.

Incorrect sensor

readings.

Improper sensor

wiring.

Correct sensor

wiring—see

section 4.

Always reports very

low temperature

and/or humidity.

Probe not connected

properly.

Connect probe
properly—see

section 2.