Operating procedures ups-s2 – Vanguard UPS S2 User Manual
Page 9
Operating Procedures
UPS-S2
6
4.0 PRETEST SETUP
4.1 Operating Voltages
The UPS-S2
™ operating voltages are pre-set for 90-130Vac, 50/60Hz or 210-240Vac, 50/60Hz.
at the factory.
To set the UPS-S2 for 120Vac operation, the High Range jumper is connected to terminal 7 of
the variac.
To set the UPS-S2 for 240Vac operation, the high Range jumper is connected to terminal 6 of the
variac.
Figure 3 Variac Terminals
4.2 UPS-S2 output voltage
The UPS-S2 output voltage is shown in table below:
Table 3 Typical UPS-S2 Output Voltage with 120Vac input
RANGE SETTING
HIGH RANGE
LOW RANGE
AC VOLTAGE OUTPUT
0-270Vac
0-120Vac
DC VOLTAGE OUTPUT
0-360Vdc
0-150Vdc
Table 4 Typical UPS-S2 Output Voltage with 240Vac input
RANGE SETTING
HIGH RANGE
LOW RANGE
AC VOLTAGE OUTPUT
0-250Vac
0-220Vac
DC VOLTAGE OUTPUT
0-360Vdc
0-260Vdc
120Vac Setting
240Vac Setting
- Resistor Transducer Adapter 9095-UC (7 pages)
- Accu-Ohm 200 S2 (4 pages)
- Accu-Trans (28 pages)
- ATO-400 (43 pages)
- ATO-400P (44 pages)
- Auto-Ohm (22 pages)
- Auto-Ohm 100_200 s2 (31 pages)
- Auto‐Ohm 200 S3 (66 pages)
- DMOM-100 (35 pages)
- DMOM-100_200 s2 (42 pages)
- DMOM-200 (33 pages)
- Herculito (17 pages)
- ATRT-01 S2 (59 pages)
- ATRT-01_01B S3 (88 pages)
- ATRT-01_01B_01D (31 pages)
- ATRT-03_03A (114 pages)
- ATRT-03_03A S2 (147 pages)
- CVT-765 (46 pages)
- Tri-Phase (155 pages)
- CBCT (14 pages)
- CBPS-300 (16 pages)
- CT-3500 (24 pages)
- CT-3500 S2 (53 pages)
- CT-6500 (69 pages)
- CT-6500 S2 (82 pages)
- CT-7000 (83 pages)
- CT-7000 S2 (108 pages)
- CT-7000 S3 (137 pages)
- CT-7500 (76 pages)
- CT-7500 S2 (110 pages)
- CT-8000 (120 pages)
- CT-8000 S3 (145 pages)
- DigiTMR (86 pages)
- DigiTMR S2 (123 pages)
- DigiTMR S2 PC (31 pages)
- MCCB-250 (17 pages)
- EZCT-2000 (68 pages)
- EZCT-2000 (45 pages)
- EZCT-2000A (103 pages)
- EZCT-2000B (118 pages)
- EZCT-2000C Plus (119 pages)
- EZCT-S2 (66 pages)
- EZCT-S2A (98 pages)
- IRM-5000P (58 pages)