3.5.2. Testing a Three Phase Transformer
Follow the steps below to test a three phase transformer:
a. Start from the “START-UP” menu:
Press the
[1]
key (TEST XFMR).
b. The following screen will be displayed:
Select a three-phase transformer test by pressing the corresponding key (
[2]
to
[5]
). For
this example, press the
[2]
key (dT-Y) to select the Delta to Y phase transformer test.
c. The following screen will be displayed:
Select the transformer configuration by pressing the corresponding key (
[1]
to
[6]
). For
this example, press the
[1]
key (Dyn1).
d. The following screen will be displayed:
1. YES
Press the
[1]
key (YES) if you would like to enter the transformer name plate
voltage values. The following screen will be displayed:
Type the H winding name plate voltage value using the numeric keypad. The
screen will be updated as shown:
ENTER H WINDING
NAME-PLATE VOLTAGE:
V
XFMR NAME PLATE VLTG
1. YES
2. NO
dT-Y XFMR CONFIG:
1.Dyn1 2.Dyn3
3.Dyn5 4.Dyn7
5.Dyn9 6.Dyn11
XFMR CONFIGURATION:
1.SNGL PHS 2.dT-Y
3.Y-dT 4.dT-dT
5.Y-Y
1.TEST XFMR 06/02/10
2.SETUP 15:33:10
3.CALCULATOR