Self purging your rg5410a, Self purge / auto evacuate – TIF RG5410A Refrigerant Recovery Machine User Manual
Page 12

SELF PURGING YOUR RG5410A
PROCEDURE FOR PURGING REMAINING REFRIGERANT FROM THE RG5410A
1. Close the ports of the system being serviced that
are connected to the input port of the RG5410A.
2. Close the input port on the RG5410A.
3. Turn off the RG5410A.
4. Turn the Recover/Purge valve to the Purge posi-
tion.
5. Restart the RG5410A.
6. Run until desired vacuum is achieved.
7. Close the ports on the recovery tank and the
RG5410A.
8. Turn the RG5410A off.
9. Return the Recover/Purge valve to the Recover
position.
10.Disconnect and store all hoses.
11.Replace the in-line filter on your RG5410A
after every job.
SELF PURGE / AUTO EVACUATE
To change from Recovery mode to Purge follow the steps below:
1. Close the Input port
2. Turn the unit off (to prevent high pressure shutoff).
3. Switch to Purge position.
4. Restart the unit.