CyberChiller Series Installation, Operation & Maintenance Manual

4-4

SYMPTOM

PROBABLE CAUSE

RECOMMENDATION

Head Pressure is too Low

a. Loss of refrigerant (indicated by

Repair leak and recharge system.

bubbles in the sight glass).

Suction Pressure too Low

a. Expansion valve stuck in the open

Repair or replace valve.

position (indicated by abnormally cold
suction line).

b. Low charge, flash gas in liquid line

Repair leak and recharge system.

(indicated by bubbles in sight glass).

c. Clogged drier/strainer (feels cool to

Replace drier/strainer.

the touch).

d. Obstructed expansion valve (indicat

Replace valve.

ed by loss of capacity).

e. Loss of control fluid from expansion

Replace valve or control head.

valve control head (indicated by
bubbles in the sight glass).

Compressor Fails to Start

a. Temperature setpoint too high.

Adjust to desired temperature.

b. Compressor internal protector

Check compressor for short circuit or

is open.

ground.

c. Complete loss of refrigerant charge

Locate and repair leak. Recharge

(low pressure safety switch).

system.

d. Condenser pressure too high (high

Check condenser for obstructions.

pressure safety switch).

e. Minimum off time has not expired.

Wait for time to expire.

System Short of Capacity

a. Low refrigerant (indicated by

Check for leaks Repair and recharge

bubbles in sight glass).

system.

b. Expansion valve stuck or

Remove valve and clear obstruction or

obstructed (short cycling or

replace valve.

continuous running).

c. Clogged drier/strainer (feels cold).

Replace with new drier/ strainer.

Compressor Short Cycles

a. Low line voltage causing

Check power source for cause of low

compressor to overheat.

line voltage.

b. Reduced flow rate.

Check pump and strainer.

c. Lack of refrigerant

Check for leak. Repair and recharge

system.