CyberChiller Series Installation, Operation & Maintenance Manual

SYMPTOM

PROBABLE CAUSE

RECOMMENDATION

4-3

Condenser Pressure

a. Non-condensable gas or air in the

Recover system and recharge. Install

too High

system.

new drier/strainer.

b. Condenser air intake is blocked.

Remove debris and clean condenser.

c. Overcharge of refrigerant.

Reclaim excess refrigerant from system.

d. Condenser fan not operating.

Check pressure/temperature operating
switches and motor. Replace as needed.

e. Condenser pressure regulating

Adjust to obtain correct pressure.

valve setting too high.

3. Air in system - bleed system.

4. Check all strainers and clean if
needed.

Condenser Pressure

a. Loss of refrigerant (indicated by

Locate and repair leak. Recharge

too Low

bubbles in sight glass).

system.

b. Condenser fan controls not set

Adjust or repair controls.

properly.

Noisy Compressor

a. Expansion valve stuck in open

Ensure feeder bulb is tight on suction

position (abnormally cold suction line).

line. Check operation and superheat.

b. Broken compressor valve

Replace compressor.

(compressor knocking, suction
pressure rises faster than 2lbs/min
after shutdown).

c. Worn or scarred compressor

Replace compressor.

bearings.

d. Liquid slugging.

System overcharged. Reclaim excess
refrigerant.

e. Scroll compressor not properly

Phase correctly at main power source.

phased.

DO NOT REWIRE COMPRESSOR.

Head Pressure Too High

a. Low condenser airflow. (Indicated by

Open air passages. Clean coil. Check

excessive warm air leaving the

condenser fan(s).

condenser fan).

b. Air or other non-condensible gas

Reclaim system and recharge. Install a

in system

new drier strainer.

c. Overcharge of refrigerant.

Reclaim excess refrigerant from system.

d. Condenser/drycooler fans not on.

Check main voltage power source to unit.