Installation in a ups, Overview – American Power Conversion AP9619 User Manual
Page 10

6
Installation and Quick Start
Installation in a UPS
Overview
You can install the Management Card in a card slot in a 
Smart-UPS, Matrix-UPS, or Symmetra. For a Silcon UPS, the 
Management Card installs in a Silcon Triple Expansion 
Chassis (AP9604S).
Step 1: Turn off 
all power 
(Smart-UPS or 
Matrix-UPS)
You do not need to turn power off for a Symmetra UPS.
Smart-UPS
1. Turn off the
equipment that 
connects to the 
UPS.
2. Disconnect the
UPS from its AC 
input source.
3. Press the OFF
button on the 
UPS for 
approximately 
five seconds to 
turn off the DC 
(battery) power.
Matrix-UPS
1. Turn off the
equipment that 
connects to the 
UPS.
2. Turn off the
circuit breaker on 
the rear panel of 
the UPS.
Caution
Damage to the
UPS
or Management Card can
result if you do not remove all
AC
and
DC
power
from a Smart-UPS or Matrix-UPS model UPS.
Test